CAN module (MXI2) RPDO6: Telegram not received or faulty [0x00b00005]
CAN module (MXI2) RPDO7: Telegram not received or faulty [0x00b00006]
CAN module (MXI2) RPDO8: Telegram not received or faulty [0x00b00007]
CAN module (MXI2) PDO manager: Faulty configuration [0x00b00008]
Module ID (decimal)
Error ID (decimal)
176: CAN module in MXI2: CAN-PDO handler
5
Response (Lenze setting printed in bold)
Setting:
C14591/6
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: CAN-IN 6
error
• Incorrect PDO telegram length.
• Transmission error.
• Time monitoring of the PDOs has tripped.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate trouble in the environment (e. g. EMC).
• Select a different time monitoring or switch off time
monitoring.
Module ID (decimal)
Error ID (decimal)
176: CAN module in MXI2: CAN-PDO handler
6
Response (Lenze setting printed in bold)
Setting:
C14591/7
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: CAN-IN 7
error
• Incorrect PDO telegram length.
• Transmission error.
• Time monitoring of the PDOs has tripped.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate trouble in the environment (e. g. EMC).
• Select a different time monitoring or switch off time
monitoring.
Module ID (decimal)
Error ID (decimal)
176: CAN module in MXI2: CAN-PDO handler
7
Response (Lenze setting printed in bold)
Setting:
C14591/8
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: CAN-IN 8
error
• Incorrect PDO telegram length.
• Transmission error.
• Time monitoring of the PDOs has tripped.
• Set correct telegram length for CAN master
(transmitter).
• Eliminate trouble in the environment (e. g. EMC).
• Select a different time monitoring or switch off time
monitoring.
Module ID (decimal)
Error ID (decimal)
176: CAN module in MXI2: CAN-PDO handler
8
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: CAN-PDO
configuration error
• Faulty project download.
• Invalid CAN settings according to DS301V402 in the
Engineer or PLC Designer.
• Mapping variables have incorrect CANopen indices
according to DS405.
• Repeat download.
• Correct CAN settings in the project and regenerate
project.