C00601 | resp. to encoder comm. error, C00604 | resp. to device overload > c00123, C00606 | resp. to motor overload > c00127 – Lenze E94AxPExxxx User Manual
Page 826: C00604, Occu, T in, C00606, C00601, 15 parameter reference
15
Parameter reference
15.2
Parameter list | C00601
826
Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00601
C00604
C00606
Parameter | Name:
C00601 | Resp. to encoder comm. error
Data type: UNSIGNED_32
Index: 23974
d
= 5DA6
h
Response to activation of encoder monitoring
• For the use of the encoder as motor encoder: If an error occurs, the safe operation of the motor is no longer
ensured, therefore for safety reasons the "Fault" response should always be set!
Selection list
(Lenze setting printed in bold)
1 Fault
2 Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble
13 Quick Stop open loop by trouble
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00604 | Resp. to device overload > C00123
Data type: UNSIGNED_32
Index: 23971
d
= 5DA3
h
Response if adjustable "I x t" warning threshold (
) is reached.
Selection list
(Lenze setting printed in bold)
1 Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1
Parameter | Name:
C00606 | Resp. to motor overload > C00127
Data type: UNSIGNED_32
Index: 23969
d
= 5DA1
h
Response if adjustable "I
2
x t" warning threshold (
) is reached.
Selection list
(Lenze setting printed in bold)
1 Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer
Scaling factor: 1