MXI2: Wrong module [0x00680011]
Incorrect memory module [0x00680012]
Incorrect safety module [0x00680013]
Power section was changed [0x00680014]
MXI1: Module has been changed [0x00680015]
Module ID (decimal)
Error ID (decimal)
104: Module identification
17
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The extension module in module slot MXI2 is not
supported by the operating system.
• Use a different module.
• Please contact Lenze.
Module ID (decimal)
Error ID (decimal)
104: Module identification
18
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The memory module is not supported by the operating
system.
• Use a different module.
• Please contact Lenze.
Module ID (decimal)
Error ID (decimal)
104: Module identification
19
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The safety module is not supported by the operating
system.
• Use a different module.
• Please contact Lenze.
Module ID (decimal)
Error ID (decimal)
104: Module identification
20
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The power section has been changed since the last mains
switching.
(Only information or warning locked if the hardware
type has also changed.)
Module ID (decimal)
Error ID (decimal)
104: Module identification
21
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
The extension module in module slot MXI1 has been
changed since the last mains switching.
(Only information or warning locked if the hardware
type has also changed.)