Analog input 1: master current < 4 ma [0x007d0000, Plc configuration invalid [0x007d0001, 0x007d0000 – Lenze E94AxPExxxx User Manual
Page 697: 0x007f0002, 0x007f0003, 0x007d0001, 14 diagnostics & fault analysis
Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06
697
14
Diagnostics & fault analysis
14.7
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Analog input 1: Master current < 4 mA [0x007d0000]
PLC configuration invalid [0x007d0001]
Communication error between device and device module [0x007f0002]
Communication with module in MXI1 interrupted [0x007f0003]
Module ID (decimal)
Error ID (decimal)
125: Processing of analog inputs/outputs
0
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Master current is in the impermissible range -4 ... +4 mA,
e. g. due to a cable break or a defective master current
value encoder.
• Only for parameterisation as master current input
(see
Remove cable break.
Module ID (decimal)
Error ID (decimal)
125: Processing of analog inputs/outputs
1
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An invalid control configuration has occurred.
Load a different application.
Module ID (decimal)
Error ID (decimal)
127: Interface to the intelligent communication module
2
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Communication between the controller and extension
module is interrupted, e.g. due to disturbances in the
ambience (EMC), defective hardware, or loose contact.
• This monitoring is designed for safe process data
communication.
• Eliminate EMC interference.
• Switch off controller, correctly plug in the module,
switch on the controller again.
• Mains switching or restart of the controller,
respectively.
• Replace module/controller.
• Please contact Lenze if the problem occurs again.
Module ID (decimal)
Error ID (decimal)
127: Interface to the intelligent communication module
3
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Communication between the controller and the
extension module in module slot MXI1 cannot be
established.
• Switch off controller, plug module correctly in module
slot MXI1, switch on controller again.
• If the problem occurs again, replace the module.