Analog input 1: master current < 4 ma [0x007d0000, Plc configuration invalid [0x007d0001, 0x007d0000 – Lenze E94AxPExxxx User Manual

Page 697: 0x007f0002, 0x007f0003, 0x007d0001, 14 diagnostics & fault analysis

background image

Lenze · 9400 Servo PLC· Reference manual · DMS 4.0 EN · 11/2013 · TD05/06

697

14

Diagnostics & fault analysis

14.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Analog input 1: Master current < 4 mA [0x007d0000]

PLC configuration invalid [0x007d0001]

Communication error between device and device module [0x007f0002]

Communication with module in MXI1 interrupted [0x007f0003]

Module ID (decimal)

Error ID (decimal)

125: Processing of analog inputs/outputs

0

Response (Lenze setting printed in bold)

Setting:

C00598

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Master current is in the impermissible range -4 ... +4 mA,

e. g. due to a cable break or a defective master current

value encoder.

• Only for parameterisation as master current input

(see

C00034

).

Remove cable break.

Module ID (decimal)

Error ID (decimal)

125: Processing of analog inputs/outputs

1

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An invalid control configuration has occurred.

Load a different application.

Module ID (decimal)

Error ID (decimal)

127: Interface to the intelligent communication module

2

Response (Lenze setting printed in bold)

Setting:

C01501

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Communication between the controller and extension

module is interrupted, e.g. due to disturbances in the

ambience (EMC), defective hardware, or loose contact.

• This monitoring is designed for safe process data

communication.

• Eliminate EMC interference.

• Switch off controller, correctly plug in the module,

switch on the controller again.

• Mains switching or restart of the controller,

respectively.

• Replace module/controller.

• Please contact Lenze if the problem occurs again.

Module ID (decimal)

Error ID (decimal)

127: Interface to the intelligent communication module

3

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Communication between the controller and the

extension module in module slot MXI1 cannot be

established.

• Switch off controller, plug module correctly in module

slot MXI1, switch on controller again.

• If the problem occurs again, replace the module.