Script – IDEC High Performance Series User Manual
Page 977
![background image](/manuals/350385/977/background.png)
WindO/I-NV2 User’s Manual
20-13
3 Global Script
20
Script
5
Click Trigger Condition tab.
6
With Trigger Type, select the condition to execute the script.
■
Rising-edge
Script is executed when trigger device changes from 0 to 1. Specify a bit device or a bit of a word device for Device.
Click
to display the Device Address Settings dialog box. For the device address configuration procedure, refer to
Chapter 2 “5.1 Device Address Settings” on page 2-67.
■
Falling-edge
Script is executed when trigger device changes from 1 to 0. Specify a bit device or a bit of a word device for Device.
Click
to display the Device Address Settings dialog box. For the device address configuration procedure, refer to
Chapter 2 “5.1 Device Address Settings” on page 2-67.
■
Always ON
The script is executed on every scan of the MICRO/I.
■
Fixed Period
Script is executed at set intervals. Specify Period in seconds.
7
Click OK to close the Global Script dialog box.
For HG1F/2F/2S/3F/4F, this concludes the Global Script configuration.
8
Click Close on the Global Script Settings dialog box.
This concludes the Global Script configuration.