5 specifications, Specifications -62 – IDEC High Performance Series User Manual
Page 1378
![background image](/manuals/350385/1378/background.png)
5 HG3F/4F
34-62
WindO/I-NV2 User’s Manual
5.5 Specifications
■
Applicable Standards
■
Environmental Specifications
■
Electrical Specifications
■
Construction Specifications
Safety Standard
UL508, UL1604, CSA C22.2 No.213 (c-UL)
EMC Standard
IEC/EN 61000-6-4, IEC/EN 61131-2
Type No.
HG3F
HG4F
Operating Ambient Temperature
0 to 50°C
0 to 45°C
Operating Relative Humidity
20 to 85% RH (no condensation)
Storage Ambient Temperature
-20 to +60°C
Storage Relative Humidity
20 to 85% RH (no condensation)
Altitude (Operation)
0 to 2000m
Pollution Degree
2
Corrosion Immunity
Free from corrosive gases
Rated Operating Voltage
24V DC
Power Consumption
25W maximum
Power Voltage Range
19.2V DC to 28.8V DC
Allowable Momentary Power
Interruption
10 ms maximum
Inrush Current
15A maximum (cold start)
Dielectric Strength
AC1500V, 10mA, 1 minute (between power and earth terminals)
Insulation Resistance
10 MΩ minimum (500V DC megger) (between power and earth terminals)
Vibration Resistance
10 to 55 Hz, 9.8 m/s
2
[2 hours each in 3 axes] (IEC60068-2-6)
Shock Resistance
147 m/s
2
, 11 ms
[5 shocks each in 3 axes] (IEC60062-2-27)