5 specifications, Specifications -6 – IDEC High Performance Series User Manual
Page 1322
![background image](/manuals/350385/1322/background.png)
1 HG2G-S/-5S
34-6
WindO/I-NV2 User’s Manual
1.5 Specifications
■
Applicable Standards
■
Environmental Specifications
■
Electrical Specifications
■
Construction Specifications
Type No.
HG2G-S
HG2G-5S
Safety Standard
UL508, UL1604,
CSA C22.2 No.142 (c-UL),
CSA C22.2 No.213 (c-UL)
UL508,
CSA C22.2 No.142 (c-UL)
EMC Standard
IEC/EN 61131-2:2007
IEC/EN 61131-2:2007
Operating Ambient Temperature
0 to 50°C
Operating Relative Humidity
10 to 90% RH (no condensation)
Storage Ambient Temperature
-20 to +60°C
Storage Relative Humidity
10 to 90% RH (no condensation)
Altitude (Operation)
0 to 2000m
Pollution Degree
2
Corrosion Immunity
Free from corrosive gases
Type No.
HG2G-S
HG2G-5S
Rated Operating Voltage
HG2G-S*22 : 24V DC
HG2G-S*21 : 12V DC
12V DC / 24V DC
Power Consumption
10W maximum
8W maximum
Power Voltage Range
HG2G-S*22 : 20.4V DC to 28.8V DC
HG2G-S*21 : 10.2V DC to 18.0V DC
10.2V DC to 28.8V DC
Allowable Momentary Power
Interruption
10 ms maximum
10 ms maximum
Inrush Current
HG2G-S*22 : 20A maximum
HG2G-S*21 : 40A maximum
40A maximum
Dielectric Strength
AC1000V, 10mA, 1 minute (between power and earth terminals)
Insulation Resistance
50 MΩ minimum (500V DC megger) (between power and earth terminals)
Vibration Resistance
5 to 8.4Hz amplitude 3.5mm,
8.4 to 150Hz acceleration 9.8m/s
2
10 times on each of three mutually perpendicular axes (100 minutes)
(IEC61131-2)
Shock Resistance
147m/s
2
, 11ms (5 shocks on each of three mutually perpendicular axes)
(IEC61131-2)