Project set tings – IDEC High Performance Series User Manual
Page 221
![background image](/manuals/350385/221/background.png)
WindO/I-NV2 User’s Manual
4-35
3 Project Settings Dialog Box
4
Project Set
tings
System Area 3
This area is for changing the MICRO/I internal clock data.
System Area 4
This area reads the MICRO/I internal clock data in one minute intervals.
Address
Bit
Function
Description
+3
3
Printing
This bit changes to 1 when sending output to the printer. This bit
automatically changes to 0 when finished sending output.
4
Transferring recipe
This bit changes to 1 when transferring recipe data. This bit
automatically changes to 0 when the transfer is finished.
5
Character input setting
complete
This bit changes to 1 when finished entering text with the
Character Input. Write 0 to character input setting clear
(address+1, bit 11) to clear this bit.
6
Character input setting cancel
This bit changes to 1 when entering text with the Character Input
is canceled. Write 0 to character input setting clear (address+1,
bit 11) to clear this bit.
7 to 15
Reserved
Address
Bit
Function
Description
+4
0 to 7
Clock data Month
Enter Month (01 to 12) as a 2 digit BCD.
8 to 15
Clock data Year
Enter Year (00 to 99) as a 2 digit BCD.
+5
0 to 7
Clock data Hour
Enter Hour (00 to 23) as a 2 digit BCD.
8 to 15
Clock data Day
Enter Day (01 to 31) as a 2 digit BCD.
+6
0 to 7
Clock data Second
Enter Second (00 to 59) as a 2 digit BCD.
8 to 15
Clock data Minute
Enter Minute (00 to 59) as a 2 digit BCD.
+7
0 to 14
Reserved
Enter 0 in the reserved area.
15
Update
Write 1 to this bit to write the entered data (address+4 to +6, bits
0 to 15) to the MICRO/I internal clock data.
When the value of the update bit (address+7, bit 15) becomes 1, the clock data is updated as a whole.
Year, month, day, hour, minute, and second cannot be set individually.
Address
Bit
Function
Description
+8
0 to 7
Clock data Month
These bits store the current Month (01 to 12) value as a 2 digit BCD.
8 to 15
Clock data Year
These bits store the current Year (00 to 99) value as a 2 digit BCD.
+9
0 to 7
Clock data Hour
These bits store the current Hour (00 to 23) value as a 2 digit BCD.
8 to 15
Clock data Day
These bits store the current Day (01 to 31) value as a 2 digit BCD.
+10
0 to 7
Reserved
8 to 15
Clock data Minute
These bits store the current MICRO/I clock data Minute (00 to 59).
+11
0 to 3
Clock data Day of Week
These bits store the current Day of Week value as a 2 digit BCD. The
relationship between the day of the week and the value is as follows.
00: Sunday
01: Monday
02: Tuesday
03: Wednesday
04: Thursday
05: Friday
06: Saturday
4 to 15
Reserved