Operations subject to password protection, Use r ac counts and the sec urit y function – IDEC High Performance Series User Manual
Page 1057
![background image](/manuals/350385/1057/background.png)
WindO/I-NV2 User’s Manual
23-7
1 Overview
23
Use
r Ac
counts and the Sec
urit
y Function
●
Operations Subject to Password Protection
If you configure a password for a user account assigned to a security group to protect access to data, access to data
is password protected. The operations that are subject to password protection and the security group that the
password is valid for are as follows.
*1 External memory inserted into the MICRO/I (HG2G-5F, HG3G/4G, HG2F/3F/4F only)
*2 HG2G-5F, HG3G/4G only
*3 HG3F/4F only
Operations subject to password protection
Security group that the password is valid for
Administrator
Operator
Reader
Data editing
Opening projects
YES
NO
NO
Reusing screens
YES
NO
NO
Modifying data
Downloading project data
YES
NO
NO
Downloading PLC programs
from external
memory
to hosts
YES
NO
NO
Downloading data to external memory
YES
NO
NO
Downloading data to external memory
while the
MICRO/I is running
YES
YES
NO
Uploading project data
YES
NO
NO
Uploading PLC programs
from hosts to external memory
YES
NO
NO
Uploading external memory data
YES
YES
YES
Deleting all data
YES
NO
NO
Deleting external memory data
YES
NO
NO
Formatting external memory
YES
NO
NO
Switching to the system menu
YES
NO
NO
Displaying Device Monitor
YES
YES
NO
Copying files from a USB flash drive to an SD memory card
YES
YES
NO
Copying files from an SD memory card to a USB flash drive
YES
YES
YES
Executing the USB Autorun function
YES
NO
NO
Remotely monitoring the MICRO/I state from a web
browser terminal
YES
YES
YES
Remotely operating the MICRO/I state from a web
browser terminal
YES
YES
NO
Opening Device Monitor on a web browser terminal
and reading device values
YES
YES
YES
Opening Device Monitor on a web browser terminal
and changing the values of internal devices
YES
YES
NO
• For the HG2G-S/-5S/-5F and the HG3G/4G, you can set a dedicated password. In the Security dialog
box, on the Options tab, select the Use Password to open a Project check box, and then set the
password. The dedicated password is applicable to the following operations:
- Opening projects
- Reusing screens
- Opening projects after uploading project data
- Opening projects after uploading data on external memory
• To password protect operations, the lowest level security group out of the security groups enabled with a
password must be assigned to a user account.
The security levels, from highest to lowest, are Administrator > Operator > Reader.
Example: To password protect the operation to display Device Monitor, assign the Operator security
group to a user account. If a user account assigned to the Operator security group does not
exist, the operation is not password protected.