Communic ation – IDEC High Performance Series User Manual
Page 151
WindO/I-NV2 User’s Manual
3-49
5 User Communication
3
Communic
ation
■
Conversion Type
After calculating the data using the specified calculation type, select the type of conversion for the data from the
following.
■
Number of bytes
After converting according to the specifed conversion type, select 1 or 2 for the number of bytes for transmission
data.
Example: BCC for transmission command data
This example describes the case of transmitting the BCC calculation result from the following transmission data as
BCC data.
• Calculation Start Position and Calculation End Position
When Calculation Start Position is 2 and Calculation End Position is 1: Calculates the range 1234.
• Calculation Type
• Conversion Type
When the BCC calculation result is 0004h, the converted data is as follows.
Modbus RTU (CRC):
CRC-16 (Generating polynomial:x
16
+x
15
+x
2
+1) is calculated according to the following
procedure. Conversion Type: No Conversion, Number of bytes: 2
1. Obtain an exclusive OR (XOR) of 1 byte data at Calculation Start Position and FFFFh.
2. If the least significant bit of the result of step 1 is 0, shift to the right by one bit. If the
bit is 1, shift to the right by 1 bit and obtain XOR of the result and the value (A001h).
3. Repeat step 2 to shift 8 times.
4. Obtain XOR of the next one byte of data and the result of step 3.
5. Repeat steps 2 through 4 until the data at Calculation End Position is processed.
6. Send the result of step 5 in the order of the lower byte and upper byte.
Example: 1234h→34h, 12h
Binary (HEX) to ASCII
Considers the data as binary-coded hexadecimal number and converts it to ASCII data.
No conversion:
No conversion is performed.
XOR:
31h^32h^33h^34h^=04h
ADD:
31h+32h+33h+34h=CAh
ADD (2's Complement): Inverts the bit of CAh+1=36h
Modbus ASCII (LCR):
BA → 42h, 41h
Modbus RTU (CRC):
BA30h → BAh, 30h
1
(31h)
4
(34h)
5
(35h)
2
(32h)
STX
(02h)
3
(33h)
BCC
CR
(0Dh)
1
(31h)
4
(34h)
5
(35h)
2
(32h)
STX
(02h)
3
(33h)
BCC
CR
(0Dh)
(1)
(2)
(3)
(4)
(5)
(6)
Calculation Start Position:
(5)
(4)
(3)
(2)
(1)
(0)
Calculation End Position:
Data used for BCC calculation
0004h
Binary (HEX) to ASCII
0
(30h)
Data
4
(34h)
0004h
No conversion
00h
Data
04h