IDEC High Performance Series User Manual
Page 228
3 Project Settings Dialog Box
4-42
WindO/I-NV2 User’s Manual
When USB2(USB-A) is selected under Interface Configuration
When USB1(USB-B) is selected under Interface Configuration
When SERIAL 1 is selected under Interface Configuration
• The connection status for TCP clients and the TCP server can be checked with the value of the HG special
registers (LSD). The connection is disconnected when 0. The connection is connected when 1.
LSD67-0: Connection status for User Communication 1 set to Ethernet interface
LSD67-1: Connection status for User Communication 2 set to Ethernet interface
LSD67-2: Connection status for User Communication 3 set to Ethernet interface
• To forcibly disconnect the connection with TCP clients and the TCP server, set the value of the HG special
registers (LSD) from 0 to 1.
LSD68-0: User Communication 1 set to Ethernet interface
LSD68-1: User Communication 2 set to Ethernet interface
LSD68-2: User Communication 3 set to Ethernet interface
• When using the MICRO/I as UDP, the MICRO/I cannot automatically identify and reply to the host's IP
address and port number. UDP broadcasting is also not supported.
• For TCP client and TCP server, make a 1:1 connection between the MICRO/I and the host for one user
communication setting.
• When the Change IP Address and Port Number by Device check box is selected, the changed IP
address and port number are reflected when data is next sent.
Protocol:
Selects the protocol used by the USB interface (USB2) Type A from the following.
N/A, User Communication 1, User Communication 2, User Communication 3
This communication interface is not used when N/A is selected.
Protocol:
Selects the protocol used by the USB interface (USB1) Mini-B as N/A or Printer.
This communication interface is not used when N/A is selected.
Protocol:
Selects the protocol used by Serial Interface 1 from the following.
N/A, Host Communication, O/I Link Master, O/I Link Slave, User Communication 1,
User Communication 2, User Communication 3, Sub Host Communication
This communication interface is not used when N/A is selected.
Baud Rate:
Selects the communication speed with the host from the following.
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
The baud rate that can be configured varies based on Protocol.
Data Bits:
Selects the data length as 7 or 8.
This option can only be configured when Host Communication, User Communication 1, User
Communication 2, User Communication 3, or Sub Host Communication is selected for
Protocol.
Stop Bits:
Selects the stop bits as 1 or 2.
This option can only be configured when Host Communication, User Communication 1, User
Communication 2, User Communication 3, or Sub Host Communication is selected for
Protocol.
Parity:
Selects the parity from the following.
None, Odd, Even
This option can only be configured when Host Communication, User Communication 1, User
Communication 2, User Communication 3, or Sub Host Communication is selected for
Protocol.
Flow Control:
Selects the flow control method as None or ER according to the host being used.
This option can only be configured when Host Communication is selected for Protocol.