2 Digital I/O Units
29-8
WindO/I-NV2 User’s Manual
Operation Example
Where,
• Execution interval: 100 ms
• Input refresh: 1 ms
• I/O control: 10 ms
• Output refresh: 1 ms
The execution time of the Cyclic Script is 1 + 10 + 1 = 12 ms, so the script executes normally.
The input delay can be from 5 to 105 ms, and the output delay can be from 1 to 101 ms.
Since the sleep time is 100 - 12 = 88 ms, display processing takes place every 88 ms of each scan.
Cyclic
Script
Display
processing
(88 ms)
Input refresh (1 ms)
Output refresh (1 ms)
LEX
LEY
X
I/O control
(10 ms)
Sleep
(Display
processing
executed)
Execution interval (100 ms)
Execution
interval
(100 ms)
External
input
Y
External
output
HG Digital Input
HG Digital Output
Input delay
(5 to 105 ms)
Output delay
(1 to 101 ms)