Serial interface 2, O/i link interface – IDEC High Performance Series User Manual
Page 1354
3 HG1F
34-38
WindO/I-NV2 User’s Manual
■
Communication Terminal Block (RS485/422 type: Model No.HG1F-SB22YF only)
Note that this terminal block cannot be used simultaneously with the D-sub connector.
■
Terminating Resistance Selector SW (RS485/422 type: Model No.HG1F-SB22YF only)
Setting the Terminating Resistance Selector SW to the ON side will insert and connect the terminating resistance
(330Ω) between RDA and RDB.
●
Serial interface 2
Do not connect pin 6 (EN) with any other pins except when performing maintenance communications for downloading
project data.
Connecting the maintenance communications cable to Serial interface 2 will stop the O/I Link communications.
●
O/I Link Interface
The HG1F Operator Interface can be connected to an O/I Link Unit for 1:N communication with a PLC. This allows
high-speed communication with the PLC host.
Connecting the maintenance communications cable to Serial interface 2 will stop the O/I Link communications.
Interface Specification
RS485/422
Connector
Terminal Block 5 pin
Recommended cable
0.3mm
2
Twisted-pair shielded cable
Conductor resistance: 85Ω/km maximum
Shield resistance: 20Ω/km maximum
No.
Name
Function
1
SDA
Send Data A
2
SDB
Send Data B
3
RDA
Receive Data A
4
RDB
Receive Data B
5
SG
Signal Ground
1
5
ON
OFF
Interface Specification
RS232C
Connector
Mini DIN 8 pin
No.
Name
I/O
Function
1
RS
OUT
Request to Send
2
ER
OUT
Data terminal ready
3
SD
OUT
Send Data
4
RD
IN
Receive Data
5
DR
IN
Data set ready
6
EN
IN
Use set ready
7
SG
-
Signal Ground
8
NC
-
No connection
6
3
4
7
8
5
2
1
Recommended cable
0.3mm
2
Twisted-pair shielded cable
Conductor resistance: 85Ω/km maximum
Shield resistance: 20Ω/km maximum