Project set tings – IDEC High Performance Series User Manual
Page 217
![background image](/manuals/350385/217/background.png)
WindO/I-NV2 User’s Manual
4-31
3 Project Settings Dialog Box
4
Project Set
tings
■
Storage Method of 32-bit Numerical Data
Selects the handling method for device values when BIN32(+), BIN32(+/-), BCD8, or float32 is selected for
Data Type from the following.
■
Use Large Password Screen
Select this check box to display the Password Screen at a large size.
*1 Advanced mode only
from Upper word:
Device values are read from and written to the upper order word.
Example: When Data Type for the Numerical Input is BIN32(+) and the numerical value
12345678 (hex) was entered and written to destination device LDR 100
from Lower word:
Device values are read from and written to the lower order word.
Example: When Data Type for the Numerical Input is BIN32(+) and the numerical value
12345678 (hex) was entered and written to destination device LDR 100
for FC3A/FC4A/FC5A:
The byte order varies based on device type.
This option can only be configured when the host I/F driver Manufacturer is IDEC and
Protocol is OpenNet,MicroSmart,SmartAXIS Pro/Lite(RS232C/485).
• Device types handled as from upper word
Data Register, Timer (Current), Counter (Current), Timer (Preset), Counter (Preset),
Special Data Register
• Device types handled as from lower word
Input (Word), Output (Word), Internal Relay (Word), Link Register, Special Internal Relay
(Word), Shift Register (Word)
Device
Stored value
LDR 100
1234 (hex)
Upper word
LDR 101
5678 (hex)
Lower word
Device
Stored value
LDR 100
5678 (hex)
Upper word
LDR 101
1234 (hex)
Lower word