beautypg.com

Configuring the rio – Rockwell Automation GMLC Reference Manual User Manual

Page 84

background image

Publication GMLC-5.2 - November 1999

Configuring Your Remote I/O Interface

47

When you use the RIO adapter you can control and monitor certain
aspects of the motion controller from a PLC or SLC. RIO uses two
transfer mechanisms:

To the PLC, the motion controller appears as ¼, ½, ¾, or a full remote
rack on the RIO link. The following table shows the number of user-
defined discrete I/O that is available depending on the rack size.

Configuring the RIO

To configure the RIO interface:

1. At the Configure Control Options dialog box, select RIO.

To:

Use:

Exchange real-time data using discrete inputs and
outputs.

Discrete transfers.

Transfer parameter values, recipes, status, and
other non time-critical data for display purposes.

Block transfers.

Rack size:

Inputs:

Outputs:

To make this part the starting
group, select:

1st Quarter

4

4

0, 2, 4, or 6

Half

36

36

0, 2, or 4

3rd Quarter

68

68

0 or 2

Full

100

100

0