Publication GMLC-5.2 - November 1999

555

0 (false) if not.

When Axis_module_hard_fault_1394 = 1, Drive_hard_fault_1394 = 1.

The occurrence of one of the following underlying faults triggers the
Axis_module_hard_fault_1394:

Axis_bus_loss_fault_1394

Axis_Drive_over_temp_fault_1394

Axis_it_fault_1394

Axis_power_fault_1394

To clear this fault, you must clear the underlying fault with a Reset Fault
block, set to Reset 1394.

In the Tag Explorer, select both Axis System Variables and the desired
physical axis, then select Axis_module_hard_fault_1394 in the Tag
Window.

System Module Hard Fault 1394

System_module_hard_fault_1394 is a logical (Boolean) variable, with a
value of:

1 (true) if the 1394 system module has detected a fault condition, and

0 (false) if not.

When System_module_hard_fault_1394 = 1, Drive_hard_fault_1394 = 1.

The occurrence of one of the following underlying faults triggers the
System_module_hard_fault_1394:

System_bus_over_voltage_flt_1394

System_bus_under_voltage_flt_1394

System_control_power_fault_1394

System_ground_fault_1394