Rockwell Automation 8-545 Plug In Solid State Relay User Manual
Installation instructions photoswitch

INSTALLATION INSTRUCTIONS
PHOTOSWITCH
PLUG IN SOLID STATE RELAY, BULLETIN 8-545/8-585
IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. FOR ADDITIONAL INFORMATION REFER TO PUBLICATION PGĆ9000
BULLETIN NUMBER
TYPE
VOLTAGE SUPPLY
LOAD CURRENT
LEAKAGE
(off State)
RESPONSE TIME
(off State)
8-545
Triac
75-140-VAC
1A
6 mA
8 ms
8-585
F.E.T
0-120 VAC/DC
30mA
10 µA
1 ms
8-545
SPECIFICATIONS
Line Transient Protection
MOV varistor
. . . . . . . . . . . . . . . . . . .
Approvals
UL Listed and CSA Certified
. . . . . . . . . . . . . . . . . . . .
Contracts
1 Normally Open
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ambient Temperature Range
–20
°F to 135°F (–28°C to 57°C)
. .
Load Current
Continuous
1 A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50% (Max) Duty Cycle
2 A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10% (Max) Duty Cycle
4 A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Surge 1% (Max) Duty Cycle
10 A
. . . . . . . . . . . . . . . . . . . . . . . .
Input (control) voltage to operate
14–30VDC
. . . . . . . . . . . . . . . .
Input (control) current to operate
3 – 6 mA
. . . . . . . . . . . . . . . .
Input to output isolation
1000 Megohms and 1500 VAC
. . . . . . .
ALL 22 SERIES BASES
ALL 42RL SERIES CONTROLS
TERMINALS
1C
1NO
1NC
LOAD 75-140 VAC
TERMINALS
2C
2NO
2NC
LOAD 75-140 VAC
LOAD
LOAD
EXTERNAL CONNECTION DIAGRAM
INTERNAL SCHEMATIC
INPUT
OUTPUT
N.O.
B
A
6
9
14V MIN
TO
TERMINALS
+
-
10A FUSE
8-585
SPECIFICATIONS
Overvoltage Protection
MOV varistor
. . . . . . . . . . . . . . . . . . . . .
Approvals
UL Listed and CSA Certified
. . . . . . . . . . . . . . . . . . . .
Contracts
Form A (SPST) Normally Open
. . . . . . . . . . . . . . . . . . .
Ambient Temperature Range
–40
°F to 150°F (–40°C to 65°C)
. .
Maximum Operating Voltage
± 200VDC or Peak AC
. . . . . . . . .
Maximum Continuous Load Current
30mA
. . . . . . . . . . . . . . . .
Maximum Peak Load Current
100mA
. . . . . . . . . . . . . . . . . . . . .
Short Circuit Load Protection
None
. . . . . . . . . . . . . . . . . . . . . .
Minimum Load Current
None
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximum On Resistance
70 Ohms
. . . . . . . . . . . . . . . . . . . . . . . . .
Minimum Voltage Input for Reliable Operation
17VDC
. . . . . . .
Input Current Drain
25 mA at 30VDC
. . . . . . . . . . . . . . . . . . . . .
Isolation Voltage
2500 VAC
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EXTERNAL CONNECTION DIAGRAM
ALL 22 SERIES BASES
1C
1NO
1NC
TO PROGRAMMABLE
CONTROLLER
INTERFACE
ALL 42RL SERIES CONTROLS
AND 60-1691 MULTI-MODULE OUTPUT BASE
2C
2NO
2NC
TO PROGRAMMABLE
CONTROLLER
INTERFACE
INTERNAL SCHEMATIC
N.O.
B
A
6
9
TO
TERMINALS
(+)
(-)