beautypg.com

Rockwell Automation GMLC Reference Manual User Manual

Page 584

background image

Publication GMLC-5.2 - November 1999

547

When CNET_fault_code > 0, CNET_fault = 1, and Global_fault = 16 (if
no higher global faults are active).

Note: There are two CNET plug card LEDs – one for channel A and

one for channel B. Because these LEDs are internal to the CNET
fiber optic plug card, they are not readily visible on this type of
plug card.

If a cable is connected to the network access port (NAP) of the CNET
plug card, the state of the LEDs is meaningless.

Plug Fault

A CNET Communications fault (CNET_fault_code = 4) indicates that a
problem internal to the CNET plug card has caused the card to fail. This
fault occurs during CNET initialization.

When CNET_fault_code = 4, Global_fault = 16, CNET_fault = 1,
CNET_status = 3 and both CNET plug card LEDs are solid red.

Note: There are two CNET plug card LEDs – one for channel A and

one for channel B. Because these LEDs are internal to the CNET
fiber optic plug card, they are not readily visible on this type of
plug card.

If a cable is connected to the network access port (NAP) of the CNET
plug card, the state of the LEDs is meaningless.

To handle or clear this fault:

Recycle power to the CNET plug card, or

2

Incorrect Network
Configuration

Flashing Red/
Green

1

Incorrect Node Configuration

Flashing Red

0

No Fault

Solid Green

Fault Code

Fault Condition

LED