Fault Variables

In the Tag Explorer select General System Variables, then select
RIO_fault_code in the Tag Window.

When RIO_fault_code

4, RIO_status = 1 (OfFLine), the LED on the

RIO option is

OFF

, and Global_fault = 10 (RIO Fault). The different types

of RIO faults are explained following.

Initialization Failure

An RIO initialization failure fault (RIO_fault_codem = 9) indicates that
the RIO option failed to pass its power-up diagnostics. When
RIO_fault_code = 9, RIO_status = 1 (Offline), the LED on the RIO option
is OFF, and Global_fault = 10 (RIO Fault).

Setup Failure

An RIO setup failure fault (RIO_fault_code = 7 or 8) indicates that the
RIO option could not be set up by the motion controller as configured.
When RIO_fault_code = 7 or 8, RIO_status = 1 (Offline), the LED on the
RIO option is OFF, and Global_fault = 10 (RIO Fault). Check that the
RIO setup data for the adapter or scanner is correct.

Fault
Code

Description

Ad

a

p

te

r

Sc

an

n

e

r

9

Initialization Failure

8

Setup Failure

7

Setup Failure

6

Failed Getting Inputs

5

Failed Sending Outputs

4

Scanner Failure

3

Failed Getting Data

2

Failed BTW Request

1

Failed Sending BTR

0

No RIO Default