beautypg.com

2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 90

background image

2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-62

Special D

Function

ES

EX

SS

SA

SX

SC

EH

EH2

SV

Off

Ø

On

STOP

Ø

RUN

RUN

Ø

STOP

Attribute Latched Default

SC: low word of present value of Y11 pulse output

0 - - R NO 0

D1350

EH2/SV: CH2 pulse output. When M1536 = On, it
refers to the deceleration time

- - - R/W YES 100

SC: high word of present value of Y11 pulse output

0 - - R NO 0

D1351

EH2/SV: CH3 pulse output. When M1537 = On, it
refers to the deceleration time

- - - R/W YES 100

EH/EH2/SV: start/end frequency of the 2

nd

group

pulse output CH1 (Y2, Y3)

- YES

D1352

SC: start/end frequency of Y11 output

200

- - R/W

NO

200

EH/EH2/SV: acceleration/deceleration time of the
2

nd

group pulse output CH1 (Y2, Y3)

- YES

100

D1353*

SC: acceleration/deceleration time of Y11 output

200

- - R/W

NO 200

D1355*

Starting reference for Master to read from Salve
ID#1

- - - R/W YES

H’1064

D1356*

Starting reference for Master to read from Salve
ID#2

- - - R/W YES

H’1064

D1357*

Starting reference for Master to read from Salve
ID#3

- - - R/W YES

H’1064

D1358*

Starting reference for Master to read from Salve
ID#4

- - - R/W YES

H’1064

D1359*

Starting reference for Master to read from Salve
ID#5

- - - R/W YES

H’1064

D1360*

Starting reference for Master to read from Salve
ID#6

- - - R/W YES

H’1064

D1361*

Starting reference for Master to read from Salve
ID#7

- - - R/W YES

H’1064

D1362*

Starting reference for Master to read from Salve
ID#8

- - - R/W YES

H’1064

D1363*

Starting reference for Master to read from Salve
ID#9

- - - R/W YES

H’1064

D1364*

Starting reference for Master to read from Salve
ID#10

- - - R/W YES

H’1064

D1365*

Starting reference for Master to read from Salve
ID#11

- - - R/W YES

H’1064

D1366*

Starting reference for Master to read from Salve
ID#12

- - - R/W YES

H’1064

D1367*

Starting reference for Master to read from Salve
ID#13

- - - R/W YES

H’1064

D1368*

Starting reference for Master to read from Salve
ID#14

- - - R/W YES

H’1064