8 Application Instructions API 100-149

DVP-PLC Application Manual

8-36

API Mnemonic Operands

Function

125

D LN P

Natural Logarithm of Binary Floating Point

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T

C

D

E

F

S

*

*

*

D

*

DLN, DLNP: 9 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

: Device for operation source D: Device for operation result

Explanations:

1. See the specifications of each model for their range of use.

2. Flags: M1020 (zero flag); M1021 (borrow flag); M1022 (carry flag)

3. This instruction performs natural logarithm “LN” operation by S: LN[S + 1, S]=[D + 1, D

4. Only positive values are valid for S. When designating D registers, the data should be 32-bit and the operation

should be performed in floating point system. Therefore, S should be converted into a floating point value.

5. e

D

= S .The content in D = lnS; S = designated source data.

6. If the absolute value of the result > maximum floating point available, the carry flag M1022 = On.

7. If the absolute value of the result < minimum floating point available, the borrow flag M1021 = On.

8. If the result = 0, the zero flag M1020 = On.

Program Example:

1. When M0 = On, convert (D1, D0) into binary floating point and store it in register (D11, D10).

2. When M1= On, use register (D11, D10) as the real number for LN operation and store the binary floating point

result in register (D21, D20).

3. When M2 = On, convert the binary floating point (D21, D20) into decimal floating point (D30 × 10

[D31]

) and store

it in register (D31, D30).

M0

RST

M1081

M1

DLN

D10

D20

M2

DEBCD

D20

D30

DFLT

D0

D10

Remarks:

For floating point operations, see “5.3 Handling of Numeric Values”.