2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-11

2.4 Numbering and Functions of Auxiliary Relays [M]

No. of auxiliary relays (in decimal)

ES/EX/SS series MPU:

General purpose

M0 ~ M511, M768 ~ M999, 744 points. Fixed to be non-latched.

Latched

M512 ~ M767, 256 points. Fixed to be latched.

Auxiliary relay M

Special purpose

M1000 ~ M1279, 280 points. Some are latched.

Total 1,280

points

SA/SX/SC series MPU:

General purpose

M0 ~ M511, 512 points. Fixed to be non-latched.

Latched

M512 ~ M999, M2000 ~ M4095, 2,584 points. Can be modified to be
non-latched by setting up parameters.

Auxiliary relay M

Special purpose

M1000 ~ M1999, 1000 points. Some are latched.

Total 4,096

points

EH/EH2/SV series MPU:

General purpose

M0 ~ M499, 500 points. Can be modified to be latched by setting up
parameters.

Latched

M500 ~ M999, M2000 ~ M4095, 2,596 points. Can be modified to be
non-latched by setting up parameters.

Auxiliary relay M

Special purpose

M1000 ~ M1999, 1,000 points. Some are latched.

Total 4,096

points

Functions of auxiliary relays:

Both auxiliary relay M and output relay Y have output coils and contact A, B, and there is no limitation on the

times of using the contact. You can use auxiliary relay M to assemble a control loop, but it cannot directly drive the

external load. There are three types of auxiliary relays:

1. General purpose auxiliary relay: If the relay encouters power cut during the operation of the PLC, its status will

be reset to Off and stay Off when the power is on again.

2. Latched auxiliary relay: If the relay encounters power cut during the operation of the PLC, its status will be

retained and stay at the status before the power cut when the power is on again.

3. Special purpose auxiliary relay: Every relay of this kind has its specific function. Do not use undefined special

purpose auxiliary relay. See 2.10 for special puspose auxiliary relay of all series MPU and 2.11 for its functions.

2.5 Numbering and Functions of Step Relays [S]

No. of step relays (in decimal)

ES/EX/SS series MPU:

Initial latched

S0 ~ S9, 10 points. Fixed to be latched.

Zero return
latched

S10 ~ S19, 10 points, used with IST instruction. Fixed to be latched.

Step relay S

Latched

S20 ~ S127, 108 points. Fixed to be latched.

Total 128

points

SA/SX/SC series MPU:

Initial

S0 ~ S9, 10 points. Fixed to be non-latched.

Zero return

S10 ~ S19, 10 points, used with IST instruction. Fixed to be non-latched.

General purpose S20 ~ S511, 492 points. Fixed to be non-latched.

Latched

S512 ~ S895, 384 points. Can be modified to be non-latched by setting
up parameters.

Step relay S

Alarm

S896 ~ S1023, 128 points. Fixed to be latched.

Total

1,024 points