7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-48

API Mnemonic

Operands

Function

63

INCD

Incremental Drum Sequencer

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T

C

D

E

F

S

1

*

*

*

*

*

*

*

S

2

*

D

*

*

*

n

*

*

INCD: 9 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

1

: Start device in the data table S

2

: No. of counter D: Start No. of the devices for the comparison results

n

: Number of data for comparison

Explanations:

1. When

S

1

designates KnX, KnY, KnM and KnS, it has to designate K4.

2. In the 16-bit instruction, S

2

has to designate C0 ~ C198 and will occupy 2 consecutive No. of counters.

3. Range

of

n

: 1 ~ 64

4. See the specifications of each model for their range of use.

5. Flag: M1029 (instruciton execution completed)

6. INCD instruction is for the relative control of the multiple output pulses generated by the present value in the

counter.

7. The present value in S

2

is compared with S

1

. S

2

will be reset to 0 whenever a comparison is completed. The

current number of data processed in temporarily stored in S

2

+ 1.

8. When n data have been processed, M1029 will be On for one scan period.

Program Example:

1. Before the execution of INCD instruction, use MOV instruction to write all the set values into D100 ~ D104 in

advance. D100 = 15, D101 = 30, D102 = 10, D103 = 40, D104 = 25.

2. The present value in C10 is compared against the set values in D100 ~ D104. The present value will be reset to

0 whenever a comparison is completed.

3. The current number of data having been processed is temporarily stored in C11.

4. The number of times of reset is temporarily stored in C11.

5. Whenever the content in C11 pluses 1, M10 ~ M14 will also correspondingly change. See the timing diagram

below.

6. After the 5 groups of data have been compared, M1029 will be On for one scan period.

7. When X0 goes from On to Off, C10 and C11 will both be reset to 0 and M10 ~ M14 will all be Off. When X0 is On

again, the instruction will start its execution again from the beginning.

INCD

D100

C10

M10

K5

X0

CNT

C10

K100

M1013