beautypg.com

2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 89

background image

2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-61

Special D

Function

ES

EX

SS

SA

SX

SC

EH

EH2

SV

Off

Ø

On

STOP

Ø

RUN

RUN

Ø

STOP

Attribute Latched Default

D1334

Low word of the remaining number of pulses of the
2

nd

group pulses CH1 (Y2, Y3)

0 - - R NO 0

D1335

High word of the remaining number of pulses of the
2

nd

group pulses CH1 (Y2, Y3)

0 - - R NO 0

D1336

Low word of the present value of the 1

st

group

pulses CH0 (Y0, Y1)

(EH2/SV are latached above EH_V1.2)

- - - R YES 0

D1337

High word of the present value of the 1

st

group

pulses CH0 (Y0, Y1)

(EH2/SV are latached above EH_V1.2)

- - - R YES 0

D1338

Low word of the present value of the 2

nd

group

pulses CH1 (Y2, Y3)

(EH2/SV are latached above EH_V1.2)

- - - R YES 0

D1339

High word of the present value of the 2

nd

group

pulses CH1 (Y2, Y3)

(EH_V1.2 and above are latached)

- - - R YES 0

EH/EH2/SV: start/end frequency of the 1

st

group

pulse output CH0 (Y0, Y1)

- YES

D1340

SC: start/end frequency of Y10 output

200

- - R/W

NO

200

D1341

Low word of max. output frequency

- - - R YES

H’04D0

D1342

High word of max. output frequency

Fixed as
200KHz

- - - R YES

3

EH: acceleration/deceleration time for the 1

st

group

pulse output CH0 (Y0, Y1)

- YES

100

D1343*

SC: acceleration/deceleration time of Y10 output

200

- - R/W

NO 200

D1344

Low word of the number of compensation pulses of
the 1

st

group pulses CH0 (Y0, Y1)

- - - R/W YES

0

D1345

High word of the number of compensation pulses of
the 1

st

group pulses CH0 (Y0, Y1)

- - - R/W YES

0

D1346

Low word of the number of compensation pulses of
the 2

nd

group pulses CH1 (Y2, Y3)

- - - R/W YES

0

D1347

High word of the number of compensation pulses of
the 2

nd

group pulses CH1 (Y2, Y3)

- - - R/W YES

0

SC: low word of present value of Y10 pulse output

0 - - R NO 0

D1348

EH2/SV: CH0 pulse output. When M1534 = On, it
refers to the deceleration time

- - - R/W YES 100

SC: high word of present value of Y10 pulse output

0 - - R NO 0

D1349

EH2/SV: CH1 pulse output. When M1535 = On, it
refers to the deceleration time

- - - R/W YES 100