beautypg.com

Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 300

background image

7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-16

M1000

DCNT

C251

K200

M0

DHSCR

K100

C251

Y10

C251

SET

Y0

Program Example 2:

When DHSCR instruction designates the same high speed counter, and the present value in the high speed counter

C251 changes from 999 to 1,000 or 1,001 to 1,000, C251 will be reset to Off.

M1000

DCNT

C251

K200

DHSCR K1000

C251

C251

1,000

200

Affected by scan time

C251 output contact

Not affected by scan time

Remarks:

1.

DVP all series MPU support high speec counters. For the limitation on the use of instructions, see remarks of

API 53 DHSCS for more details.

2.

M1261 of EH/EH2/SV series MPU designates the external reset modes of the high speed counter. Some high

speec counters have input points for external reset; therefore, when the input point is On, the present value in

the corresponding high speed counter will be cleared to 0 and the output contact will be Off. If you wish the reset

to be executed immediately by the external output, you have to set M1261 to be On.

3.

M1261 can only be used in the hardware high speed counter C241 ~ C255.

4. Example:

a) X2 is the input point for external reset of C251.

b) Assume Y10 = On.

c) When M1261 = Off and X2 = On, the present value in C251 will be cleared to 0 and the contact of C251 will

be Off. When DHSCR instruction is executed, there will be no counting input and the comparison result will

not output. The external output will not execute the reset; therefore Y10 = On will remain unchanged.

d) When M1261 = On and X2 = On, the present value in C251 will be cleared to 0 and the contact of C251 will

be Off. When DHSCR instruction is executed, there will be no counting input but the comparison result will

output. Therefore, Y10 will be reset.

M1000

DCNT

C251

K1000

DHSCR

K0

C251

Y10

X10

M1261