beautypg.com

2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 64

background image

2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-36

Special

M

Function

ES

EX

SS

SA

SX

SC

EH

EH2

SV

Off

Ø

On

STOP

Ø

RUN

RUN

Ø

STO

P

Attribute Latched Default

M1056

Inhibiting I6□□

Off

- - R/W NO Off

M1057

Inhibiting I7□□

Off

- - R/W NO Off

M1059

Inhibiting I010 ~ I060

Off

- - R/W NO Off

M1060

System error message 1

Off

- - R NO Off

M1061

System error message 2

Off

- - R NO Off

M1062

System error message 3

Off

- - R NO Off

M1063

System error message 4

Off

- - R NO Off

M1064

Incorrect use of operands

Off

Off

- R NO

Off

M1065 Syntax

error

Off

Off

- R NO

Off

M1066 Loop

error

Off

Off

- R NO

Off

M1067* Calculation

error

Off

Off

- R NO

Off

M1068* Calculation error locked (D1068)

Off

- - R NO Off

M1070

ES/SA: Y1 time base switching for PWM instruction
(On: 100us; Off: 1ms)

EH/EH2/SV: Y0 time base switching for PWM
instruction (On: 100us; Off: 1ms)

EH_V1.2 and above/EH2/SV: when On, D1371 will
decide the time base)

Off

- - R/W NO Off

M1071

Y2 time base switching for PWM instruction (On:
100us; Off: 1ms)

EH_V1.2 and above/EH2/SV: when On, D1372 will
decide the time base)

Off

- - R/W NO Off

M1072

Executing PLC RUN instruction

Off

On

Off

R/W NO Off

M1075

Error occurring when writing FLASH card

Off

- - R NO Off

M1076* Real time clock malfunction

Off

- - R NO Off

M1077

Battery in low voltage, malfunction or no battery

Off

- - R NO Off

M1078

Immediately stopping Y0 pulse output for PLSY
instruction

Off

- - R/W NO Off

M1079

Immediately stopping Y1 pulse output for PLSY
instruction

Off

- - R/W NO Off

M1080

Requesting COM2 monitoring

Off

- - R NO Off

M1081

Changing direction for FLT instruction

Off

- - R/W NO Off

M1082

Real time clock has been changed

Off

- - R NO Off

M1083

Allowing interruption subroutine in FROM/TO
instructions

Off

- - R/W NO Off

M1084*

Detecting bandwidth (only available in
ES/EX/SS_V6.4, SA/SX_V1.6, SC_V1.4 and above)

Off

Off

Off

R/W NO Off