Delta Electronics DVP Series PLC DVP04TC-H2 User Manual
Warning, Introduction, Specifications
Warning
Please read this instruction sheet carefully before use.
Switch off the power before wiring.
DVP04TC-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device
(e.g. key or specific tools are required to open the enclosure) in case danger and damages on the device may occur.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all
the wiring again before switching on the power.
DO NOT touch any terminal when the power is switched on.
Make sure the ground termnial
is correctly grounded in order to prevent electromagnetic interference.
Keep the wire as short as possible between RTD and PLC and the power wire as far away as possible from I/O wire
to prevent interference.
When setting the
thermocouple temperature sensor mode, please make sure that the setting of CR#1 is correct, or it will cause
serious errors.
Introduction
Model Explanation & Peripherals
Thank you for choosing Delta’s DVP series PLC. DVP04TC-H2 is able to receive 4 points of external
thermocouple temperature sensors (J-type, K-type, R-type, S-type, T-type) and convert them into 14-bit
digital signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, the data in
DVP04TC-H2 can be read or written. There are 49 16-bit control registers (CR) in DVP04TC-H2.
DVP04TC-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F).
Product Profile (Indicators, Terminal Block, I/O Terminals)
Unit: mm
D
-
L
+
L
-
L
+
2
4
V
0
V
L
-
L
+
L
-
L
+
L
-
D
+
S
L
D
8
S
L
D
S
L
D
S
L
D
C
H
1
C
H
2
C
H
3
C
H
4
R
S
-4
8
5
1
DIN rail (35mm)
6
Terminals
2
Connection port for extension unit/module
7
Mounting hole
3
Model name
8
I/O terminals
4
POWER, ERROR, A/D indicator
9
Mounting port for extension unit/module
5
DIN rail clip
ENGLISH
External Wiring
CH1
CH4
DC/ DC
5V
AG
+15V
-15V
AG
24+
0V
L -
*2
*3
+
-
10 k
MUX
+
-
L -
Thermoc ouple
Thermoc ouple
Shielding
cable *1
Shielding
cable *1
Cold-Junction
Compensation
System
grounding
Terminal of
power module
Earth
(100 or less)
*1: The wiring used for analog input should adopts the connection cable or shielding cable of thermocouple temperature sensor
J-type / K-type / R-type / S-type / T-type and should be separated from other power cable or wirings that may cause interference.
The screw torque of the terminal should be 1.95 kg-cm (1.7 in-lbs).
*2: Terminal SLD is the ground location for noise suppression.
*3: Please connect the
terminal on both the power module and DVP04TC-H2 to the system earth point and ground the system
contact or connect it to the cover of power distribution cabinet.
Note:
DO NOT wire empty terminal . Use 60/75°C copper conductor only.
Specifications
Temperature
measurement module
Explanation
Power supply voltage
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
Analog output channel
4 channels/module
Applicable sensor types
J-type, K-type, R-type, S-type, T-type Floating thermocouple sensor
Range of input
temperature
See the table in Section
Range of digital
conversion
See the table in Section
Resolution
14 bits (0.1°C/0.18°F)
Overall accuracy
±0.5% when in full scale (25°C, 77°F)
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Response time
200ms × the number of channels
Isolation
Isolation between digital area and analog area. No isolation among channels.
Digital data format
13 significant bits out of 16 bits are available; in 2’s complement
Average function
Yes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K20
Self-diagnosis
Upper and lower bound detection/channel
Communication mode
(RS-485)
ASCII/RTU mode. Communication speed: 4,800/9,600/19,200/38,400/57,600 /115,200 bps.
ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 stop
bit (8, E, 1). RS-485 cannot be used when connected to PLC MPU.
When connected to
DVP-PLC MPU in series
The modules are numbered from 0 to 7 automatically by their distance from MPU. No. 0 is the
closest to MPU and No. 7 is the furthest. Maximum 8 modules are allowed to connect to MPU
and will not occupy any digital I/O points.
Other Specifications
Power supply
Max. rated power
consumption
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2.5W supplied by external power.
Environment
Operation/storage
1. Operation: 0°C~ 55°C (Temperature), 50 ~ 95% (Humidity), pollution degree 2
2. Storage: -25°C~ 70°C (Temperature), 5 ~ 95%
(Humidity)
Vibration/shock immunity Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Control Register
CR
#
RS-485
parameter
address
Latched
Register content
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#0
H’4096
○ R Model name
Set up by the system.
DVP04TC-H2 model code = H’6403.
You can read the model name from the program and see
if the extension module exists.
Reserved
CH4
CH3
CH2
CH1
#1
H’4097
○ R/W Thermocouple type
Take the setting of CH1 for example:
1. When (b2, b1, b0) is set as (0,0,0), choose J-type
2. When (b2, b1, b0) is set as (0,0,1), choose K-type
3. When (b2, b1, b0) is set as (0,1,0), choose R-type
4. When (b2, b1, b0) is set as (0,1,1), choose S-type
5. When (b2, b1, b0) is set as (1,0,0), choose T-type
CR#1: The working mode of the 4 channels in the sensors selected by the temperature measurement module. There are
2 modes (J-type and K-type) for each channel which can be set up separately. For example, if the user needs to set up
CH1: mode 0 (b2 ~ b0 = 100); CH2: mode 1 (b5 ~ b3 = 001); CH3: mode 0 (b8 ~ b6 = 000) and CH4: mode 1 (b11 ~ b9 =
001), CR#1 has to be set as H0208 and the higher bits (b12 ~ b15) have to be reserved. The default value = H’0000.
#2
H’4098
○ R/W CH1 average time
#3
H’4099
○ R/W CH2 average time
#4
H’409A
○ R/W CH3 average time
#5
H’409B
○ R/W CH4 average time
Range of settings in CH1 ~ CH4: K1 ~ K20. Default =K10.
Please note that when PLC MPU writes in the average
time by TO/DTO instruction, please use the rising/falling
edge contact detection instructions (LDP/LDF…) in case
you may not obtain the correct average temperature.
#6
H’409C
╳
R
Average °C temp. measured at CH1
#7
H’409D
╳
R
Average °C temp. measured at CH2
#8
H’409E
╳
R
Average °C temp. measured at CH3
#9
H’409F
╳
R
Average °C temp. measured at CH4
Average Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C
CR#6 ~ CR#9: The average Celsius temperature measured at CH1 ~ CH4 obtained from the average time settings in
CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#6 ~ CR#9 will be the average of the most
recent 10 temperature signals in Celsius at CH1 ~ CH4.
#10 H’40A0
╳
R
Average °F temp. measured at CH1
#11
H’40A1
╳
R
Average °F temp. measured at CH2
#12 H’40A2
╳
R
Average °F temp. measured at CH3
#13 H’40A3
╳
R
Average °F temp. measured at CH4
Average Fahrenheit temperature measured at CH1 ~
CH4.
Unit: 0.1°F
CR#10 ~ CR#13: The average Fahrenheit temperature measured at CH1 ~ CH4 obtained from the average time settings
in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#10 ~ CR#13 will be the average of the
most recent 10 temperature signals in Fahrenheit at CH1 ~ CH4.
#14 H’40A4
╳
R
Present °C temp. measured at CH1
#15 H’40A5
╳
R
Present °C temp. measured at CH2
#16 H’40A6
╳
R
Present °C temp. measured at CH3
#17 H’40A7
╳
R
Present °C temp. measured at CH4
Present Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C
#19 H’40A9
╳
R
Present °F temp. measured at CH1
#20 H’40AA
╳
R
Present °F temp. measured at CH2
#21 H’40AB
╳
R
Present °F temp. measured at CH3
#22 H’40AC
╳
R
Present °F temp. measured at CH4
Present Fahrenheit temperature measured at CH1 ~ CH4.
Unit: 0.1°F
CR
#
RS-485
parameter
address
Latched
Register content
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#24 H’40AE
○ R/W OFFSET value of CH1
#25 H’40AF
○ R/W OFFSET value of CH2
#26 H’40B0
○ R/W OFFSET value of CH3
#27 H’40B1
○ R/W OFFSET value of CH4
Adjustable OFFSET settings at CH1 ~ CH4.
Range: -1,000 ~ +1,000
Default = K0
Unit: 0.1°C
#30 H’40B4
╳
R
Error status
Register for storing all error status.
See the table of error status for more information.
CR#30: Error status (see the table below)
Error status
Content
b15 ~ b8
b7
b6
b5
b4
b3
b2
b1
b0
Abnormal power supply
K1 (H’1)
0
0
0
0
0
0
0
1
Wiring to empty external contact K2 (H’2)
0
0
0
0
0
0
1
0
Incorrect mode setting
K4 (H’4)
0
0
0
0
0
1
0
0
OFFSET/GAIN error
K8 (H’8)
0
0
0
0
1
0
0
0
Hardware malfunction
K16 (H’10)
0
0
0
1
0
0
0
0
Abnormal digital range
K32 (H’20)
0
0
1
0
0
0
0
0
Incorrect average times setting
K64 (H’40)
0
1
0
0
0
0
0
0
Instruction error
K128 (H’80)
Reserved
1
0
0
0
0
0
0
0
Note:
Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the
same time. 0 = normal; 1 = error.
#31 H’40B5
○ R/W Communication address setting
For setting RS-485 communication address.
Range: 01 ~ 254, Default = K1.
#32 H’40B6
○ R/W
Communication speed (baud rate)
setting
For setting up communication speed: 4,800/9,600/19,200/
38,400/57,600/115,200 bps. ASCII data format: 7-bit, even
bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1
stop bit (8, E, 1). Default: H’0002.
b0: 4,800 bps.
b1: 9,600 bps (default).
b2: 19,200 bps.
b3: 38,400 bps.
b4: 57,600 bps.
b5: 115,200 bps.
b14: High/low bit exchange of CRC checksum (only valid
in RTU mode)
b15: Switch between ASCII/RTU modes; 0 = ASCII mode
(default)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
ERR LED
CH4
CH3
CH2
CH1
#33 H’40B7
○ R/W Returning to default setting
Take the setting of CH1 for example:
1. b0 is reserved.
2. b1 is reserved.
3. When b2 is set as 1, all the settings will return to
default settings.
ERR LED definition: default of b12 ~ b15 = 1111
1. When b12 = 1, CH1 wiring to empty external contact,
ERR LED will flash.
2. When b13 = 1, CH2 wiring to empty external contact,
ERR LED will flash.
3. When b14 = 1, CH3 wiring to empty external contact,
ERR LED will flash.
4. When b15 = 1 CH2 wiring to empty external contact,
ERR LED will flash.
#34 H’40B8
○ R Firmware version
Displaying the current firmware version in hex; e.g.
version 1.0A is indicated as H’010A
#35 ~ #48
For system use
PID Control Registers
CR#
CH1 CH2 CH3 CH4
Latched
Register content
Explanation
#51
#71
#91 #111
○ R/W Temperature SV
Range: K-1,000 ~ K8,000. Default = K0.
#52
#72
#92 #112
○ R/W Sampling time (s)
Range: K1 ~ K30 (s). Default = K2.
#53
#73
#93 #113
○ R/W KP
Default = K121.
#54
#74
#94 #114
○ R/W KI
Integral constant, Default = K2,098.
#55
#75
#95 #115
○ R/W KD
Derivative constant, Default = K-29.
#56
#76
#96 #116
○ R/W Upper limit of I value
Range: K-32,760 ~ K32,760. Default = K0.
#57
#77
#97 #117
○ R/W Lower limit of I value
Range: K-32,760 ~ K32,760. Default = K0.
#58
#78
#98 #118
╳
R
I value
Current accumulated offset value. Default = K0.
#59
#79
#99 #119
○ R/W Heating/cooling control
0: Heater, 1: Cooler. Default = K0.
#60
#80 #100 #120
○ R/W Upper limit of output
Range: K-32,760 ~ K32,760. Default = K4,000.
#61
#81 #101 #121
○ R/W Lower limit of output
Range: K-32,760 ~ K32,760. Default = K0. .
#62
#82 #102 #122
╳
R
Output percentage (%)
Range: K0 ~ K1,000 (Unit: 0.1%). Default = K0.
#63
#83 #103 #123
╳
R
Output width (ms)
Width of control output, Unit: ms. Default = K0.
#64
#84 #104 #124
╳
R
Output cycle (ms)
Cycle of control output, Unit: ms. Default = K0.
#65
#85 #105 #125
╳
R
Output volume
Default = K0.
#66
#86 #106 #126
╳
R/W PID_Run/Stop
0: Stop, 1: Run. Default = K0.
#67
#87 #107 #127
╳
R/W Auto Tune
0: Disabled, 1: Auto-tuning. Default = K0.
※ CR#0 ~ CR#127: The corresponding parameter address H’4096 ~ H’4115 are for users to read/write data by
RS-485 communication. When using RS-485, the user has to separate the module with MPU first.
1. Modbus ASCII/RTU communication protocol: ASCII data format (7-bit, even bit, 1 stop bit (7, E, 1)); RTU
data format (8-bit, even bit, 1 stop bit (8, E, 1)).
2. Function: H’03 (read register data); H’06 (write 1 word datum into register); H’10 (write many word data
into register).
3. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written
by MPU through TO/DTO instruction
4. Symbols:
○: Latched.
╳
: Non-latched. R: Able to read data by FROM instruction or RS-485
communication. W: Able to write data by TO instruction or RS-485 communication.
Temperature / Digital Curve
°C/°F Temperature Measurement Mode:
Max.
Min.
Digital output
Measured
temperature input
Min.
Max.
Range of input temperature
Range of digital conversion
Thermo
-couple
Min. (°C /
°F)
Max. (°C /
°F)
Min. (°C /
°F)
Max. (°C /
°F)
J type
-100°C / -148°F
700°C / 1,292°F
K-1,000 / K-1,480
K7,000 / K12,920
K type
-100°C / -148°F 1,000°C / 1,832°F K-1,000 / K-1,480
K10,000 / K18,320
R type
-10°C / -14°F
1,700°C / 3,092°F
K-100 / K-140
K17,000 / K30,920
S type
-10°C / -14°F
1,700°C / 3,092°F
K-100 / K-140
K17,000 / K30,920
T type
-100°C / -148°F
350°C / 662°F
K-1,000 / K-1,480
K3,500 / K6,620
注意事項
請在使用之前,詳細閱讀本使用說明書。
實施配線,務必關閉電源。
本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊
∕
衝
擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意
外衝擊本體,造成危險及損壞。
交流輸入電源不可連接於輸入
∕
出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認電源配線。
請勿在上電時觸摸任何端子或進行維修。
本體上之接地端子 務必正確的接地,可提高產品抗雜訊能力。
由測溫體到溫調本體的配線路請用最短距離配線,為了避免雜訊及誘導的影響儘可能將電源線和負載配線分
開。
感測器熱電耦型式設定,請檢查 CR#1,如設定錯誤會造成量測重大誤差。
產品簡介
說明及週邊裝置
謝謝您採用台達 DVP 系列產品。DVP04TC-H2 溫度量測模組可接受外部 4 點(熱電耦溫度感測器 J, K, R, S,
T
型),將之轉換成 14 位元之數位信號。透過 DVP-PLC EH2 主機程式以指令 FROM/TO 來讀寫模組內之
資料,模組內具有 49 個 CR (Control Register) 暫存器,每個暫存器有 16 bits。
使用者可選擇攝氏溫度或華氏溫度,攝氏溫度輸入解析度為 0.1
°C
,華氏溫度輸入解析度為 0.18
°F
。
產品外觀及各部介紹
尺寸單位:mm
D
-
L
+
L
-
L
+
2
4
V
0
V
L
-
L
+
L
-
L
+
L
-
D
+
S
L
D
8
S
L
D
S
L
D
S
L
D
C
H
1
C
H
2
C
H
3
C
H
4
R
S
-
4
8
5
1
DIN 軌糟 (35mm)
6
端子
2
擴充機/擴充模組連接口
7
固定孔
3
機種名稱
8
端子配置
4
電源、錯誤及轉換指示燈
9
擴充機/擴充模組連接座
5
DIN 軌固定扣
繁體中文
外部配線
熱電耦
CH1
CH4
DC/ DC
5V
AG
+15V
-15V
AG
24+
0V
L -
L+
轉換器
系統接地點
第三種接地
接地阻抗
以下
(100
)
接至電源模
隔離線 *1
*2
*3
隔離線 *1
熱電耦
+
-
10 k
MUX
冷接點補償
組之
端
+
-
L -
L+
SLD
SLD
註 1:使用於類比輸入的配線應採用 J / K / R / S / T 型熱電耦溫度感測器之連接線或隔離線且應與其他電源線或可能引起雜訊
之接線分開。端子鏍絲扭力為 1.95 kg-cm (1.7 in-lbs)。
註 2:如果雜訊過大請將 SLD 及接地端子連接。
註 3:請將電源模組之 端及 DVP04TC-H2 溫度量測模組之 端連接到系統接地點,再將系統接點作第三種接地或接到
配電箱之機殼上。
注意:空端子 請勿配線。只能使用 60/75°C 的銅導線。
規格
溫度量測模組
規格說明
電源電壓
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
類比訊號輸出通道
4
通道/台
適合感應器形式
J-type, K-type, R-type, S-type, T-type
非接地型熱電耦感測器
輸入溫度範圍
請參閱
附表
數位轉換範圍
請參閱
附表
解析度
14 bits (0.1°C/0.18°F)
總和精密度
±0.5%
在 (25°C, 77°F) 範圍內滿刻度時。±1% 在 (0 ~ 55°C, 32 ~ 131°F) 範圍內滿刻度時。
響應時間
200ms ×
通道數
隔離方式
數位區與類比區有隔離,通道間未隔離。
數位資料格式
16
位元二補數,有效位 13 bits。
平均功能
有(CR#2 ~ CR#5 可設定,範圍 K1 ~ K20)
自我診斷功能
上下極限偵測/通道
通訊模式 (RS-485)
包含 ASCII/RTU 模式,通訊速率可選 (4,800/9,600/19,200/38,400/57,600/115,200),ASCII 模式資
料格式固定為 7-bit、偶位元、1 stop bit (7, E, 1),RTU 模式資料格式固定為 8-bit、偶位元、1 stop bit
(8, E, 1)
。當與 PLC 主機串接時,RS-485 通訊無法使用。
與 DVP-PLC 主機
串接說明
模組編號以靠近主機之順序自動編號由 0 到 7,最大可連接 8 台且不佔用數位 I/O 點數
其他規格
電源規格
額定最大消耗功率
直流 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2.5W, 由外部電源供應