7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-20

The comparison table:

32-bit data for comparison

High word

Low word

No. of Y output

On/Off indication

Table counting
register D1150

D1 (K0) D0 (K100) D2 (K10)

D3 (K1)

0

D5 (K0) D4 (K200) D6 (K11)

D7 (K1)

1

D9 (K0) D8 (K300) D10 (K10)

D11 (K0)

2

D13 (K0)

D12 (K400) D14 (K11)

D15 (K0)

3

K10: Y10

K11: Y11

K0: Off

K1: On

0→1→2→3→0

Cyclic scan

M1151

D1150

Y11

Y10

100

200

300

400

0

1

2

3

0

Present value

in C251

14. Special registers for flags and relevant settings:

Flag

Function

M1150

DHSZ instruction in multiple set values comparison mode

M1151

The execution of DHSZ multiple set values comparison mode is completed.

Special D

Function

D1150

Table counting register for DHSZ multiple set values comparison mode

Program Example 4:

1.

Program Example 4 is only applicable to EH/EH2/SV series MPU.

2.

DHSZ and DPLSY instructions are combined for frequency control. If D of DHSZ instruction is a special auxiliary

relay M1152, the present value in the counter will be able to control the pulse output frequency of DPLSY

instruction.

3.

In this mode,

- S

1

: start device in the comparison table. S

1

can only designate data register D and can be modified by E and

F. Once this mode is enabled, S

1

will not be changed even the E and F has been changed.

- S

2

: number of group data to be compared. S

2

can only designate K1 ~ K255 or H1 ~ HFF and can be

modified by E and F. Once this mode is enabled, S

2

cannot be changed. If S

2

is not within its range, error

code 01EA (hex) will display and the instruction will not be executed.

- S: No. of high speed counter (designated as C241 ~ C254).