8 Application Instructions API 100-149

DVP-PLC Application Manual

8-60

heating environment” to enhance the speed to reach SV. On the contrary, when the user finds that the control is

too fast or with too many fluctuations, select “fast heating environment” to slow down the control speed.

When bit2 ~ bit5 of S

3

+1 are all set as 1 or more than 1 environments are designated, FTC instruction will check

from bit2 to bit 5 in order and enable the function that has been set as 1. The parameter can be modified during

the control.

4. Example 1: control diagram

Fuzzy

Controller

FTC

SV

D10

D22

MV

Y0

D11

PV

+

e

PT Module

GPWM Program

Temperature

Sensor

Output D22 (MV) of FTC instruction is the input D22 of GPWM instruction, as the duty cycle of ajustable pulses.

D30 is the fixed cycle time of pulses. See below for the timing diagram of Y0 output.

D22

D30

Y0

Assume parameter settings: D10 = K1,500 (target temperature), D12 = K60 (sampling time: 6 secs.), D13 = K8

(bit3=1), D30 = K6,000 (=D12*100)

The example control program is indicated as:

M1002

MOV

K1500

D10

TO

K0

K2

K2

K1

FROM

K0

K6

D11

K1

MOV

K60

D12

MOV

K8

D13

MOV

K6000

D30

SET

M1

M1

FTC

D10

D11

D12

D22

GPWM

D22

D30

Y0

M1013

FROM

K0

K6

D11

K1

END