8 Application Instructions API 100-149

DVP-PLC Application Manual

8-3

Register DATA

Explanation

D1079 low

‘0’

30 H

D1079 high

‘0’

30 H

D1080 low

‘0’

30 H

D1080 high

‘0’

30 H

Content of
address 2104 H

PLC automatically convert
ASCII codes to numerals
and store the numeral in
D1053 = 0000 H

D1081 low

‘0’

30 H

D1081 high

‘1’

31 H

D1082 low

‘3’

33 H

D1082 high

‘6’

36 H

Content of
address 2105 H

PLC automatically convert
ASCII codes to numerals
and store the numeral in
D1054 = 0136 H

D1083 low

‘0’

30 H

D1083 high

‘0’

30 H

D1084 low

‘0’

30 H

D1084 high

‘0’

30 H

Content of
address 2106 H

PLC automatically convert
ASCII codes to numerals
and store the numeral in
D1055 = 0000 H

D1085 low

‘3’

33 H

LRC CHK 1

D1085 high

‘B’

42 H

LRC CHK 0

Program Example 2:

Communication between PLC and VFD-S series AC motor drives (RTU Mode, M1143 = On)

MOV

D1120

H87

M1002

SET

M1120

MOV

D1129

K100

M1127

RST

M1127

receiving

completed

Set up communication protocol 9600, 8, E, 1

Retain communication protocol

Set up communication time-out: 100ms

Process of receiving data

Sending/receiving of data is completed.
The flag is reset.

SET

M1122

Set up as sending flag

X0

The received data in hex are stored in D1070 ~ D1085.

SET

M1143

Set up as RTU mode

X0

MODRD

K1

H2102

Set up communication instruction
device address 01 data address H2102
data length 2 words

K2

PLC VFD-S, PLC sends: 01 03 2102 0002 6F F7

VFD-S PLC, PLC receives: 01 03 04 1770 0000 FE 5C

Registers for sent data (sending messages)

Register DATA

Explanation

D1089 low

01 H

Address

D1090 low

03 H

Function

D1091 low

21 H

D1092 low

02 H

Starting data address

D1093 low

00 H

D1094 low

02 H

Number of data (counted by words)

D1095 low

6F H

CRC CHK Low

D1096 low

F7 H

CRC CHK High