beautypg.com

2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 68

background image

2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-40

Special

M

Function

ES

EX

SS

SA

SX

SC

EH

EH2

SV

Off

Ø

On

STOP

Ø

RUN

RUN

Ø

STO

P

Attribute Latched Default

M1154*

Enabling the deceleration function of adjustable
pulse output Y0

Off

- - R/W NO Off

M1161

8-bit mode

On: in 8-bit mode

Off

- - R/W NO Off

M1162

Switching between decimal integer and binary
floating point for SCLP instruction

On: binary floating point; Off: decimal integer

Off

- - R/W NO Off

M1165

When On, the program and password on flash will be
copied to the PLC when PLC is powered. (Not
available in EH)

- - - R/W YES Off

M1166

When On, the recipe on flash will be copied to the
PLC when PLC is powered. (Not available in EH)

- - - R/W YES Off

M1167

16-bit mode for HKY input

Off

- - R/W NO Off

M1168

Designating work mode of SMOV

Off

- - R/W NO Off

M1169

Selecting PWD modes

Off

- - R/W NO Off

M1170* Enabling single step execution

Off

- - R/W NO Off

M1171* Single step execution

Off

- - R/W NO Off

M1172*

Switch for 2-phase pulse output

On: switch on

Off

Off

Off

R/W NO Off

M1173* On: continuous output

Off

- - R/W NO Off

M1174* The number of output pulses reaches the target

Off

Off

- R/W NO Off

M1175

Losing PLC parameter data (not available in EH)

- - - R YES Off

M1176

Losing the data in PLC program (not available in EH)

- - - R YES Off

M1178* Enabling VR0 rotary switch

Off

- - R/W NO Off

M1179* Enabling VR1 rotary switch

Off

- - R/W NO Off

M1184* Enabling modem function (not available in SV)

Off

- - R/W NO Off

M1185* Enabling initialization of modem (not available in SV)

Off

- - R/W NO Off

M1186* Initialization of modem fails (not available in SV)

Off

- - R/W NO Off

M1187*

Initialization of modem is completed (not available in
SV)

Off

- - R/W NO Off

M1188*

Displaying whether modem is connecting currently
(not available in SV)

Off

- - R/W NO Off

M1196

Setting up the content type in the display (for SX)

On: hex; Off: decimal

Off

- - R/W NO Off

M1197

Setting up the display of the 100ths digit (for SX)

Off

- - R/W NO Off

M1198

Setting up the display of the 10ths digit (for SX)

Off

- - R/W NO Off

M1200

Counting mode of C200 (On: counting down)

Off

- - R/W NO Off