3 Basic Instructions
DVP-PLC Application Manual
3-11
Program Example:
Ladder diagram:
Instruction code:
Operation:
LD
X0
Loading in A contact of X0
MC
N0
Enabling N0 common series connection contact
LD
X1
Loading in A contact of X1
OUT Y0 Driving
Y0
coil
:
LD
X2
Loading in A contact of X2
MC
N1
Enabling N1 common series connection contact
LD
X3
Loading in A contact of X3
OUT Y1 Driving
Y1
coil
:
MCR
N1
Disabling N1 common series connection contact
:
MCR
N0
Disabling N0 common series connection contact
:
LD
X10
Loading in A contact of X10
MC
N0
Enabling N0 common series connection contact
LD
X11
Loading in A contact of X11
OUT Y10 Driving
Y10
coil
:
MCR
N0
Disabling N0 common series connection contact
X0
Y0
MC
N0
X1
X2
Y1
MC
N1
X3
MCR
N1
MCR
N0
X10
MC
N0
Y10
X11
MCR
N0
Mnemonic Function
Program
steps
LDP
Rising-edge detection
operation
1
Controllers
ES
EX
SS
SA
SX
SC
EH
SV
X0 ~ X377 Y0 ~ Y377 M0 ~ M4095
S0 ~ S1023
T0 ~ T255
C0 ~ C255
D0 ~ D9999
Operand
9
9
9
9
9
9
-
Explanations:
The method of using LDP is the same as using LD, but the actions of the two instructions differ. LDP saves the current
content and store the detected status of rising-edge to the accumulative register.
Program Example:
Ladder diagram:
Instruction code:
Operation:
LDP
X0
Starting X0 rising-edge detection
AND
X1
Series connecting A contact of X1
X0
X1
Y1
OUT Y1
Driving
Y1
coil
Remarks:
1.
See the specification of each model for the range of operands.
2.
If the status of a designated rising-edge is On before the PLC is powered, the contact of the rising-edge will be
TRUE after PLC is powered.