DVP-PLC Application Manual

9-9

Registers for received data (responding messages)

Register

DATA

Explanation

D1070 Low

01 H

Address

D1071 Low

10 H

Function

D1072 Low

20 H

D1073 Low

00 H

Data Address

D1074 Low

00 H

D1075 Low

02 H

Number of Registers

D1076 Low

4A H

CRC CHK Low

D1077 Low

08 H

CRC CHK High

Remarks:

1.

The activation condition placed before MODRD, RDST and MODRW instructions cannot use rising-edge or

falling-edge contacts; otherwise the data stored in the registers for received data will encounter errors.

2.

Flags and special registers for MODRW instruction in RS-485 communication. (For details, see API 80 RS).

Flags

Function

M1120

For retaining communication setups. After the setup is made, changes in D1120 will be
invalid.

M1121

When Off, RS-485 is sending data.

M1122 Sending

request

M1123

Receiving is completed

M1124

Waiting for receiving data

M1125

Disable receiving status

M1126

Selecting STX/ETX system

M1127

Sending/receiving data through MODRD / RDST / MODRW instructions is completed.

M1128

Sending data…/receiving data…

M1129

Receiving data time-out

M1130 User/system

defined

STX/ETX

M1131

On when MODRD / MODWR / MODRW is converting data to hex

M1140

MODRD / MODWR / MODRW data receiving error

M1141

MODRD / MODWR / MODRW parameter error

M1142

VFD-A handy instruction data receiving error

M1143

ASCII/RTU mode selection (used with MODRD/MODWR/MODRW) (Off = ASCII mode;
On = RTU mode)

D1070 ~ D1085

When the built-in RS-485 communication instruction is executed and sends out data, the
receiving end will respond with a message and the message will be stored in D1070 ~
D1085. The user can check the registers for the messages.

D1120

RS-485 communication protocol

D1121

PLC communication address (saving PLC communication address; latched)

D1122

Remaining words of the sent data

D1123

Remaining words of the received data

D1124

Start text definition (STX)

D1125

Definition of end text 1 (ETX1)

D1126

Definition of end text 2 (ETX2)

D1129

Abnormal communication time-out. Unit: ms

D1130

Records of error codes sent back from MODBUS

D1256 ~ D1295

When the built-in RS-485 communication instruction MODRW is executed, the sent out
data will be stored in D1256 ~ D1295. The user can check whether the instruction is
correct by the contents in the registers.

D1296 ~ D1311

PLC will automatically convert the ASCII data stored in the register designated by the user
into hex format.