7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7 - 1

API Mnemonic

Operands

Function

50

REF P

Refresh

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T C D E F

D

*

*

n

* *

REF, REFP: 5 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

D

: Start device to be I/O refreshed n: Number of items to be I/O refreshed

Explanations:

1.

D

must designate X0, X10, Y0, Y10…the points whose 1s digit is “0”. See remarks for more details.

2. Range

of

n

: 8 ~ 256 (has to be the multiple of 8).

3.

See the specifications of each model for their range of use.

4.

The status of all PLC input/output terminals will be updated after the program scans to END. When the

program starts to scan, the status of the external input terminal is read and stored into the memory of the input

point. The output terminal will send the content in the output memory to the output device after END instruction

is executed. Therefore, this instruction is applicable when the latest input/output data are needed for the

operation.

Program Example 1:

When X0 = On, PLC will read the status of input points X0 ~ X17 immediately and refresh the input signals without

any input delay.

X0

REF

X0

K16

Program Example 2:

When X0 = On, the 8 output signal from Y0 ~ Y7 will be sent to output terminals and refreshed without having to wait

for the END instruction for output.

X0

REF

Y0

K8

Remarks:

The instruction only process the I/O points X0 ~ X17 and Y0 ~ Y17 of ES/EX/SS/SA/SX/SC series MPU, namely n =

K8 or n = K16.