1 Basic Principles of PLC Ladder Diagram

DVP-PLC Application Manual

1-5

Internal relay

The internal relay does not have connection with the external. It is an auxiliary relay inside the

PLC with the functions same as those of the auxiliary (middle) relay in the electric control

circuit. Every internal relay corresponds to a basic internal storage unit and can be driven by

the contacts of the input relay, contacts of the output relay and the contacts of other internal

devices. There are no limitations on the times of using the contacts of the internal relay and

there will be no output from the internal relay, but from the output point.

&

Device indication: M0, M1,…, M4095 are indicated as M and numbered in decimal form.

Step

DVP series PLC offers a step-type control program input method. STL instruction controls the

transfer of step S, which makes it easy for the writing of the control program. If you do not use

any step program in the control program, step S can be used as a internal relay M as well as an

alarm point.

&

Device indication: S0, S1,…S1023 are indicated as S and numbered in decimal form.

Timer

The timer is used for timing and has coil, contact and register in it. When the coil is On and the

estimated time is reached, its contact will be enabled (contact A closed, contact B open). Every

timer has its fixed timing period (unit: 1ms/10ms/100ms). Once the coil is Off, the contact iwlwl

be disabled (contact A open, contact B closed) and the present value on the timer will become

“0”.

&

Device indication: T0, T1,…,T255 are indicated as T and numbered in decimal form.

Different No. refers to different timing period.

Counter

The counter is used for counting. Before using the counter, you have to give the counter a set

value (i.e. the number of pulses for counting). There are coil, contact and registers in the

counter. When the coil goes from Off to On, the counter will regard it as an input of 1 pulse and

the present value on the counter will plus “1”. We offer 16-bit and 32-bit high-speed counters

for our users.

&

Device indication: C0, C1,…,C255 are indicated as C and numbered in decimal form.

Data register

Data processing and value operations always occur when the PLC conducts all kinds of

sequential control, timing and counting. The data register is used for storing the values or all

kinds of parameters. Every register is able to store a word (16-bit binary value). Double words

will occupy 2 adjacent data registers.

&

Device indication: D0, D1,…,D9,999 are indicated as D and numbered in decimal form.