beautypg.com

2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 36

background image

2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-8

Binary

(BIN)

Octal

(OCT)

Decimal

(DEC)

Binary Code Decimal

(BCD)

Hexadecimal

(HEX)

For PLC internal operation

No. of device

X, Y

Constant K,

No. of device M, S, T, C,

D, E, F, P, I

For DIP switch and 7-section

display

Constant H

0 0 0 1 0 0 0 1

21

17

0

0

0

1 0

1 1 1

11

:
:
:

:
:
:

:
:
:

:
:
:

:
:
:

0 1 1 0 0 0 1 1

143

99

1

0

0

1 1 0 0 1

63

2.3 Numbering and Functions of External Input/Output Contacts [X] / [Y]

No. of input/output contacts (in octal):

The No. of input and output contacts on the PLC MPU starts from X0 and Y0. The range of the No. varies upon

the number of points on the MPU. For I/O extension units, the No. of input and output contacts is calculated according

to its connection sequence with the MPU.

ES/EX/SS series MPU:

Model

DVP-14ES DVP-14SS DVP-20EX DVP-24ES

DVP-32ES

DVP-40ES

DVP-60ES

I/O Extension Unit

Input X

X0 ~ X7

(8 points)

X0 ~ X7

(8 points)

X0 ~ X7

(8 points)

X0 ~ X17

(16 points)

X0 ~ X17

(16 points)

X0 ~ X27

(24 points)

X0 ~ X43

(36 points)

X20/30/50 ~ X177

(Note)

Output Y

Y0 ~ Y5

(6 points)

Y0 ~ Y5

(6 points)

Y0 ~ Y5

(6 points)

Y0 ~ Y7

(8 points)

Y0 ~ Y17

(16 points)

Y0 ~ Y17

(16 points)

Y0 ~ Y27

(24 points)

Y20/30 ~ Y177

(Note)

Note:

The input points on I/O extension units start from X20 and output points from Y20, except input points on

DVP-40ES start from X30 and output from Y20; input points on DVP-60ES start from X50 and output from Y30. The No. of
input/output points on the I/O extension units increases by 8’s multiple. If the number of points is less than 8, it will be
counted as 8.

SA/SX/SC serues MPU:

Model

DVP-10SX (Note1)

DVP-12SA

DVP-12SC

I/O Extension Unit (Note 2)

Input X

X0 ~ X3 (4 points)

X0 ~ X7 (8 points)

X0 ~ X5, X10 ~ X11 (8 points)

X20 ~ X177

Output Y

Y0 ~ Y1 (2 points)

Y0 ~ Y3 (4 points)

Y0 ~ Y1, Y10 ~ Y11 (4 points)

Y20 ~ Y177

Note 1:

Besides 4DI and 2DO, SX series MPU has also 2AI (12-bit) and 2AO (12-bit) of analog input/output.

Note 2:

SX/SA/SC series MPU share the extension units with SS series MPU. The input points on I/O extension units start

from X20 and output points start from Y20. The calculation on the No. of I/O points is the same as that in SS series.

EH series MPU:

Model

DVP-16EH

DVP-20EH

(Note 1)

DVP-32EH

(Note1, 2)

DVP-40EH

DVP-48EH

DVP-64EH

DVP-80EH

I/O

Extension

Unit (Note 3)

Input X

X0 ~ X7

(8 points)

X0 ~ X13

(12 points)

X0 ~ X17

(16 points)

X0 ~ X27

(24 points)

X0 ~ X27

(24 points)

X0 ~ X37

(32 points)

X0 ~ X47

(40 points)

X※~X377

Output Y

Y0 ~ Y7

(8 points)

Y0 ~ Y7

(8 points)

Y0 ~ Y17

(16 points)

Y0 ~ Y17

(16 points)

Y0 ~ Y27

(24 points)

Y0 ~ Y37

(32 points)

Y0 ~ Y47

(40 points)

Y※~Y377

Note 1:

The output type of 20EH00T and 32EH00T is transistor, among which Y0 and Y2 are high-speed transistor output

(200KHz) and other outputs are normal transistor output (10KHz). The output type of other MPUs with 16/48/64/80 points is
transistor and all outputs are normal transistor output (10KHz).
Note 2:

The terminal layouts of 32EH00T, 32EH00R and 32EH00M are different. See the instruction sheets of EH series

MPU. In 32EH00M, CH0 (Y0, Y1) and CH1 (Y2, Y3) are high-speed differential output.
Note 3:

The start No. of the input and output points on the I/O extension unit resumes from the last No. in the MPU. The start

No. of input points on the I/O extension unit of DVP-16EH and DVP-20EH start from X20 and output points start from Y20.
The No. on the I/O extension unit are in sequence, with max. input point No. X377 and max. output point No. Y377.