2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-9

EH2 series MPU:

Model DVP-16EH2

DVP-20EH2

(Note 1)

DVP-32EH2

(Note1)

DVP-40EH2

(Note 2)

DVP-48EH2 DVP-64EH2 DVP-80EH2

I/O Extension

Unit (Note 3)

Input X

X0 ~ X7

(8 points)

X0 ~ X13

(12 points)

X0 ~ X17

(16 points)

X0 ~ X27

(24 points)

X0 ~ X27

(24 points)

X0 ~ X37

(32 points)

X0 ~ X47

(40 points)

X※~X377

Output Y

Y0 ~ Y7

(8 points)

Y0 ~ Y7

(8 points)

Y0 ~ Y17

(16 points)

Y0 ~ Y17

(16 points)

Y0 ~ Y27

(24 points)

Y0 ~ Y37

(32 points)

Y0 ~ Y47

(40 points)

Y※~Y377

Note 1:

The output type of 20EH00T2 and 32EH00T2 is transistor, among which Y0 and Y2 are high-speed transistor output

(200KHz) and other outputs are normal transistor output (10KHz). The output type of other MPUs with 16/48/64/80 points is
transistor and all outputs are normal transistor output (10KHz).
Note 2:

The output type of 40EH00T2 is transistor, among which CH0 (Y0, Y1), CH1 (Y2, Y3), CH2 (Y4) and CH3 (Y6) are

high-speed transistor output (200KHz). The output type of other output points is normal transistor output (10KHz).
Note 3:

The numbering of the I/O points on EH2 series MPU is the same as that of EH series MPU.

SV series MPU:

Model

DVP-28SV (Note 1)

I/O Extension Unit (Note 2)

Input X

X0 ~ X17 (16 points)

X20 ~ X377

Output Y

Y0 ~ Y13 (12 points)

Y20 ~ Y377

Note 1:

The output type of 28SV11T is transistor output, among which CH0 (Y0, Y1), CH1 (Y2, Y3), CH2 (Y4) and CH3 (Y6)

are high-speed transistor output (200KHz); others are normal transistor output (10KHz).
Note 2:

The input points on I/O extension units start from X20 and output points start from Y20. The calculation on the No. of

I/O points is the same as that in SS series.

Input Relay X0 ~ X377

The numbering of input relays (or input terminals) is in octal form. EH series MPU can have up to 256

points and the range is: X0 ~ X7, X10 ~ X17, …, X370 ~ X377.

Output Relay Y0 ~ Y377

The numbering of output relays (or output terminals) is also in octal form. EH series MPU can have up to

256 points and the range is: Y0 ~ Y7, Y10 ~ Y17, …, Y370 ~ Y377.

Functions of input contact X

The input contact X is connected to the input device and reads the input signals into the PLC. There is no

limitation on the times of using contact A or B of input contact X in the program. On/Off of the input contact X

only changes with On/Off of the input device. You cannot use the peripheral devices (HPP or WPLSoft) to force

On/Off of the input contact X.

The special relay M1304 in SA/SX/SC/EH series MPU allows the peripheral devices HPP or WPLSoft to

force On/Off of the input contact X, but the PLC will not be able to receive external input signals at this time.

Functions of output contact Y

Output contact Y sends out On/Off signals to drive the load connected to output contact Y. There are two

types of output contacts, relay and transistor. Thereis no limitation on the times of using contact A or B of output

contact Y in the program, but the No. of output coil Y can only be used once in the program; otherwise

according to the scan principle of the PLC program, the output status will be determined by the circuit of the last

output Y in the program.