7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-64

API Mnemonic

Operands

Function

72

DSW

Digital Switch

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T

C

D

E

F

S

*

D

1

*

D

2

*

*

*

n

*

*

DSW: 9 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

: Start device for switch scan input D

1

: Start device for switch scan output D

2

: Device for storing the set value

of switch n: Groups of switches

Explanations:

1. Range

of

n

: 1 ~ 2

2. See the specifications of each model for their range of use.

3. Flag: M1029 (DSW execution completed)

4. This instruction designates 4 or 8 consecutive external input points starting from S and 4 consecutive external

input points starting from D

1

to scan read 1 or 2 4-digit DIP switches.The set values of DIP switches are stored in

D

2

. n decides to read 1 or 2 4-digit DIP switches.

5. There is no limitation on the times of using this instruction in the program. However, for SA series MPU, only one

instruction can be executed at a time. For EH series MPU, two instructions are allowed to be executed at a time.

Program Example:

1. The first group of DIP switches consist of X20 ~ X23 and Y20 ~ Y23. The second group of switches consist of

X24 ~ X27 and Y20 ~ Y23. When X10 = On, the instruction will be executed and the set values of the first group

switches will be read and converted into bin values before being stored in D20. The set values of the second

group switches will be read, converted into bin values and stored in D21.

X10

DSW

X20

Y20

D20

K2

2. When X10 = On, the Y20 ~ Y23 auto scan cycle will be On. Whenever a scan cycle is completed, M1029 will be

On for a scan period.

3. Please use transistor output for Y20 ~ Y23. Every pin 1, 2, 4, 8 shall be connected to a diode (0.1A/50V) before

connecting to the input terminals on PLC.