2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-97

+ n*6 + 4

Gap frequency of the n

th

section (GFn)

+ n*6 + 5

Target frequency of the n

th

section (TFn)

+ n*6 + 6

The lower 16 bits of the 32 bits for the target number of output pulses in the n

th

section (SEn)

+ n*6 + 7

The higher 16 bits of the 32 bits for the target number of output pulses in the n

th

section (SEn)

3. The

functions:

This function can only be used on Y0 output point and the timing chart is as follows. After filling out the

parameter table, setup M1144 to start the function (should be applied in RUN mode).

SF2

TF2

SF3

TF3

TF4

SF4

TF1

SF1

GF

GT

GT

GF

Frequency(Hz)

Time(ms)

1st section

number of

pulses

(SE1)

2nd section

number of

pulses

(SE2)

3rd section

number of

pulses

(SE3)

4th section

number of

pulses

(SE4)

4. How to use and the restrictions:

a) The start frequency and target frequency have to be ≥ 200Hz; otherwise, the function will not be executed or

complete execution.

b) The start frequency and target frequency have to be < 32,700Hz. Frequency > 32,700Hz will be executed in

32,700Hz.

c) Range of gap time: 1 ~ 32,767ms (Min. unit: ms)

d) The range of gap frequency within acceleration section: 1Hz ~ 32,700Hz; within deceleration section: -1 ~

-32,700Hz. If the gap frequency is set as 0Hz, it will fail to reach target frequency in the executed section but

in the next section when the target number of pulses is reached.

e) The target number of pulses in a section has to be > (GF × GT/1,000) × [(TF - SF)/GF]; otherwise the target

may not be reached. To correct it, the user may extend gap time or increase the target number of pulses.

f) When PLC is in RUN status and there is a high-speed instruction assigning Y0 input, the instruction will be

executed prior to other instructions.

g) After M1144 = On, if M1148 has not be reached and M1144 is “Off”, deceleration will be enabled. And if

M1154 = Off at the moment, the deceleration rule will be “decelerating 200Hz every 200ms” and M1147 will

be set. The pulse output will stop when the frequency falls under 200Hz. If M1154 = On at the moment, the

output will be executed following the gap time and frequency as set by the user. The time shall not be ≤ 0 (if ≤

0, it will follow the initial setting 200ms) and the frequency shall not be ≥ 0 (if = 0, it will follow the initial setting

-1KHz; if > 0, negative sign comes before the value).