8 Application Instructions API 100-149

DVP-PLC Application Manual

8-65

M0

K50

CVM

D0

K50

Y0

D0

T0

TMR

MOV

k-1

T0

2. Control

phases:

1) Phase

1

: When M0 = On, due to that we are not sure about there the valve is, set D0 = K-1 to deliberately

close the valve (Y0 = Off, Y1 = On) for 5 seconds and make sure the valve is at the position of 0 second

before moving on to the next step.

2) Phase

2

: When T0 = On, allow D0 = K40 to start is action. Open the valve (Y0 = On, Y1 = Off) for 4

seconds, moving the valve to the position of 4 seconds.

3) Phase

3

: Change the position of the valve and D0 = K10. Due to that the previous position was at 4

seconds, the valve shall be closed (Y0 = Off, Y1 = On) for 3 seconds, moving the valve to the position of 1

second.

4) Phase

4

: Switch off M0 and the valve will no longer move (Y0 = Off, Y1 = Off).