9 Application Instructions API 150-199

DVP-PLC Application Manual

9-93

API Mnemonic Operands

Function

196

HST P

High Speed Timer

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX KnY KnM KnS T

C

D

E

F

S

*

*

HST, HSTP: 3 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S: Condition to stop the startup of high speed timer

Explanations:

1. Range

of

S: S = K0 (H0), K1 (H1).

2. Flag:

M1015

3. When

S = 1, the high speed timer will be enabled and M1015 = On. The high speed timer starts to time and

record the present value in D1015 (min. unit: 100us).

4.

Timing range of D1015: K0 ~ K32,767. When the timing reaches K32,767, the next timing will restart from 0.

5. When

S = 0, the high speed timer will be disabled and M1015 = Off. D1015 will stop the timing immediately.

6. When

S is neither 1 nor 0, HST instruction will not be executed.

Program Example :

1.

When X10 = On, M1015 will be On. The high speed timer will start to time and record the present value in

D1015.

2.

When X10 = Off, M1015 will be Off. The high speed timer will be shut down.

X10

HST

K1

X10

HST

K0

Remarks:

1. Flag

explanations:

M1015: high speed timer start-up flag

D1015: high speed timer

2.

EH/EH2/SV series MPU do not use this instruction and use special M and special D directly for the timer.

a) Special M and special D are only applicable when PLC RUN.

b) When M1015 = On and PLC scans to END instruction, the high speed timer D1015 will be enabled. The

minimum timing unit of D1015: 100us.

c) Timing range of D1015: K0 ~ K32,767. When the timing reaches K32,767, the next timing will restart from

K0.

d) When M1015 = Off, D1015 will stop the timing when encountering END or HST instruction.

3.

SA/SX/SC series MPU do not use this instruction and use special M and special D directly for the timer.

a) Special M and special D are applicable when PLC RUN or STOP.