3 basic instructions – Delta Electronics Programmable Logic Controller DVP-PLC User Manual
Page 160
![background image](/manuals/75807/160/background.png)
3 Basic Instructions
DVP-PLC Application Manual
3-6
Mnemonic Function Program
steps
ORB
Parallel connection- loop blocks
1
Controllers
ES
EX
SS
SA
SX
SC
EH
SV
Operand
N/A
Explanations:
To perform the “OR” operation of the preserved logic results and content in the accumulative register.
Program Example:
Ladder diagram:
Instruction code:
Operation:
LD
X0
Loading in contact A of X0
ANI
X1
Connecting to contact B of X1 in series
LDI
X2
Loading in contact B of X2
AND
X3
Connecting to contact A of X3 in series
ORB
Connecting circuit block in parallel
X0
X2
Y1
X1
X3
ORB
Block A
Block B
OUT Y1
Driving
Y1
coil
Mnemonic Function
Program
steps
MPS
Store the current result of the
internal PLC operations
1
Controllers
ES
EX
SS
SA
SX
SC
EH
SV
Operand
N/A
Explanations:
To save the content in the accumulative register into the operational result (the pointer of operational result will plus
1).
Mnemonic Function
Program
steps
MRD
Reads the current result of the
internal PLC operations
1
Controllers
ES
EX
SS
SA
SX
SC
EH
SV
Operand
N/A
Explanations:
To read the operational result and store it into the accumulative register (the pointer of operational result stays intact)
.
Mnemonic Function
Program
steps
MPP
Pops (recalls and removes) the
currently stored result
1
Controllers
ES
EX
SS
SA
SX
SC
EH
SV
Operand
N/A
Explanations:
To retrieve the previous preserved logical operation result and store it into the accumulative register (the pointer of
operational result will minus 1)
.