7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-51

Program Example 2:

1. Use TMR instruction to write in 10 groups of set time.

2. Write the set values into D100 ~ D109 in advance.

3. The timing unit for timer T0 ~ T9 is 0.1 sec. The timing unit for the teaching timer is 1 sec.

4. Connect the 1-bit DIP switch to X0 ~ X3 and use BIN instruction to convert the set value of the switch into a bin

value and store it in E.

5. Store the “On” time (sec.) of X10 in D200.

6. M0 refers to the pulses generated from one scan period after the button switch of the teaching timer X10 is

released.

7. Use the set number of the DIP switch as the indirectly designated pointer and send the content in D200 to

D100E (D100 ~ D109).

M10

TMR

T0

D100

M11

TMR

T1

D101

M19

TMR

T9

D109

M1000

BIN

K1X0

E

X10

TTMR

D200

K0

X10

PLF

M0

M0

MOV

D200

D100E

Remarks:

1. For SA series MPU, TTMR instruction can be used 8 times in the program. But in a subroutine or interruption

subroutine, the instruction can only be used once.

2. For EH series MPU, there is no limitation on the times using this instruction in the program and 8 instructions can

be executed at the same time.