beautypg.com

Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 374

background image

7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-90

Fixed as END Hi = CR (0DH), END Lo = LF (0AH)

For example: Read 2 continuous data stored in the registers of the driver at address 01H (see the table below).

The start register is at address 2102H.

Inquiry message:

Responding message:

STX

‘: ’

STX

‘: ’

‘0’

‘0’

Address

‘1’

Address

‘1’

‘0’

‘0’

Function code

‘3’

Function code

‘3’

‘2’

‘0’

‘1’

Number of data

(counted by byte)

‘4’

‘0’

‘1’

Start address

‘2’

‘7’

‘0’

‘7’

‘0’

Content in start address

2102H

‘0’

‘0’

‘0’

Number of data

(counted by words)

‘2’

‘0’

‘D’

‘0’

LRC checksum

‘7’

Content of address

2103H

‘0’

CR

‘7’

END

LF

LRC check

‘1’

CR

END

LF

In RTU mode (M1143 = On)

START

See the following explanation

Address

Communication address: In 8-bit binary

Function

Function code: In 8-bit binary

DATA (n-1)

…….

DATA 0

Data:
n × 8-bit data

CRC CHK Low

CRC CHK High

CRC checksum:
16-bit CRC consists of 2 8-bit binary

END

See the following explanation

START:

For ES/EX/SS/SA/SX series MPU, no input signal can be ≥ 10ms.

See the table below for EH/EH2/SV series MPU:

Baud rate(bps) RTU timeout timer (ms) Baud rate (bps) RTU timeout timer (ms)

300 40 9,600 2
600 21

19,200 1

1,200 10 38,400 1
2,400 5 57,600 1
4,800 3 115,200 1

Address:

00H: Broadcasting to all drivers

01H: To the driver at address 01

0FH: To the driver at address 15

10H: To the driver at address 16…. And so on, maximum to the driver at address 254 (FE H)

Function code:

03H: Read contents of many registers