beautypg.com

2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 44

background image

2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-16

after the power is on again.

3. If you use MOV instruction, WPLSoft or HPP to send a value bigger than the SV to the present value register of

C0, next time when X1 goes from Off to On, the contact of counter C0 will be On and its PV will equal SV.

4. The SV in the counter can be constant K (set up directly) or the values in register D (set up indirectly, excluding

special data registers D1000~ D1999).

5. If you set up a constant K as the SV, it should be a positive value. Data register D as SV can be positive or

negative. When the PV reaches up to 32,767, the next PV will turn to -32,768.

Example:

LD X0

RST C0

LD X1

CNT

C0 K5

LD C0

OUT Y0

C0

Y0

X1

C0

K5

CNT

X0

C0

RST

a) When X0 = On, RST instruction will be

executed, PV in C0 will be “0” and the

output contact will be reset to Off.

b) When X1 goes from Off to On, the PV in

the counter will count up (plus 1).

c) When the counting of C0 reaches SV K5,

the contact of C0 will be On and PV of C0

= SV = K5. The X1 trigger signal comes

afterwards will not be accepted by C0 and

the PV of C0 will stay at K5.

X0

X1

0

1

2

3

4

5

0

Contacts Y0, C0

PV in C0

SV

32-bit general purpose addition/subtraction counters C200 ~ C234:

1. The setup range of 32-bit counter: K-2,147,483,648 ~ K2,147,483,647 (not available for ES/EX/SS series MPU).

2. Addition or subtraction of the counters is designated by On/Off status of special auxiliary relays M1200 ~ M1234.

For example, when M1200 = Off, C200 will be an addition counter; when M1200 = On, C200 will be a subtraction

counter.

3. The SV can be constant K or data register D (excluding special data registers D1000 ~ D1999). Data register D as

SV can be a positive or negative value and an SV will occupy two consecutive data registers.

4. PV in the general purpose counter will be cleared when the power of the PLC is switched off. If the counter is a

latched type, the counter will retain the PV and contact status before the power is off and resume the counting

after the power is on again.

5. When the PV reaches up to 2,147,483,647, the next PV will turn to -2,147,483,648. When the PV reaches down to

-2,147,483,648, the next PV will turn to 2,147,483,647.