2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-2

SA/SX/SC series MPU:

Type

Device

Item

Range

Function

X

External input relay

X0 ~ X177, 128 points, octal

Corresponds to external
input points

Y

External output relay

Y0 ~ Y177, 128 points, octal

Total

256

points

Corresponds to external
output points

General purpose

M0 ~ M511, 512 points (*1)

Latched*

M512 ~ M999, 488 points (*3)
M2000 ~ M4095, 2,096 points (*3)

M

Auxiliary

Relay

Special purpose

M1000 ~ M1999, 1,000 points
(some are latched)

Total

4,096

points

The contact can be
On/Off in the program.

100ms

T0 ~ T199, 200 points (*1)
T192 ~ T199 for subroutine
T250 ~ T255, 6 accumulative points
(*4)

10ms

T200 ~ T239, 40 points (*1)
T240 ~ T245, 6 accumulative points
(*4)

T Timer

1ms

T246 ~ T249, 4 accumulative points
(*4)

Total

256

points

Timer indicated by TMR
instruction. If timing
reaches its target, the T
contact of the same No.
will be On.

16-bit counting up

C0 ~ C95, 96 points (*1)
C96 ~ C199, 104 points (*3)

32-bit counting up/down

C200 ~ C215, 16 points (*1)
C216 ~ C234, 19 points (*3)

Total

235

points

For SA/SX, 32-bit
high-speed counter

C235 ~ C244, 1-phase 1 input, 9
points (*3)
C246 ~ C249, 1-phase 2 inputs, 3
points (*3)
C251 ~ C254, 2-phase 2 inputs, 4
points (*3)

Total

16

points

C Counter

For SC, 32-bit high-speed
counter

C235 ~ C245, 1-phase 1 input, 11
points (*3)
C246 ~ C250, 1-phase 2 inputs, 4
points (*3)
C251 ~ C255, 2-phase 2 inputs, 4
points (*3)

Total

19

points

Counter indicated by
CNT (DCNT) instruction.
If counting reaches its
target, the C contact of
the same No. will be On.

Initial step

S0 ~ S9, 10 points (*1)

Zero return

S10 ~ S19, 10 points (used with IST
instruction) (*1)

General purpose

S20 ~ S511, 492 points (*1)

Latched*

S512 ~ S895, 384 points (*3)

Relay (

bit)

S Step

point

Alarm

S896 ~ S1023, 128 points (*3)

Total

1,024

points

Used for SFC.

T

Present value of timer

T0 ~ T255, 256 points

When the timing
reaches the target, the
contact of the timer will
be On.

C

Present value of counter

C0 ~ C199, 16-bit counter, 200 points
C200 ~ C254, 32-bit counter, 50 points (SC: 53
points)

When the counting
reaches the target, the
contact of the counter
will be On.

General purpose

D0 ~ D199, 200 points (*1)

Latched*

D200 ~ D999, 800 points (*3)
D2000 ~ D4999, 3,000 points (*3)

Special purpose

D1000 ~ D1999, 1,000 points

D

Data
register

Index indication

E0 ~ E3, F0 ~ F3, 8 points (*1)

Total

5,000

points

Memory area for data
storage; E, F can be
used for index
indication.

Regist

er (wor

d

dat

a)

N/A File register

K0 ~ K1,599 (1,600 points) (*4)

Expanded register for
data storage.