9 Application Instructions API 150-199

DVP-PLC Application Manual

9-8

Register

DATA

Explanation

D1262 Low

‘0’

30 H

D1262 High

‘4’

34 H

Byte Count

D1263 Low

‘0’

30 H

D1263 High

‘0’

30 H

D1264 Low

‘1’

31 H

D1264 High

‘2’

32 H

Data contents 1

The content of register D50 (H12)

D1265 Low

‘1’

31 H

D1265 High

‘7’

37 H

D1266 Low

‘7’

37 H

D1266 High

‘0’

30 H

Data contents 2

The content of register D51 (H1770 = K6,000)

D1267 Low

‘3’

33 H

LRC CHK 1

D1267 High

‘0’

30 H

LRC CHK 0

Error checksum: LRC CHK (0,1)

Registers for received data (responding messages)

Register

DATA

Explanation

D1070 Low

‘0’

30 H

ADR 1

D1070 High

‘1’

31 H

ADR 0

D1071 Low

‘1’

31 H

CMD 1

D1071 High

‘0’

30 H

CMD 0

D1072 Low

‘2’

32 H

D1072 High

‘0’

30 H

D1073 Low

‘0’

30 H

D1073 High

‘0’

30 H

Data Address

D1074 Low

‘0’

30 H

D1074 High

‘0’

30 H

D1075 Low

‘0’

30 H

D1075 High

‘2’

32 H

Number of Registers

D1076 Low

‘C’

43 H

LRC CHK 1

D1076 High

‘D’

44 H

LRC CHK 0

9.

RTU Mode: When PLC is connected to VFD-S AC motor drives

PLC

Ö VFD-S, PLC sends: “01 10 2000 0002 04 0012 1770 C4 7F

VFD-S

Ö PLC, PLC receives: “01 10 2000 0002 4A 08

Registers for send data (sending messages)

Register

DATA

Explanation

D1256 Low

01 H

Address

D1257 Low

10 H

Function

D1258 Low

20 H

D1259 Low

00 H

Data Address

D1260 Low

00 H

D1261 Low

02 H

Number of Registers

D1262 Low

04 H

Byte Count

D1263 Low

00 H

D1264 Low

12 H

Data content 1

The content of register D50 (H12)

D1265 Low

17 H

D1266 Low

70 H

Data content 2

The content of register D51 (H1770 = K6,000)

D1267 Low

C4 H

CRC CHK Low

D1268 Low

7F H

CRC CHK High