2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-38

Special

M

Function

ES

EX

SS

SA

SX

SC

EH

EH2

SV

Off

Ø

On

STOP

Ø

RUN

RUN

Ø

STO

P

Attribute Latched Default

M1109* Status of SW6 on digital switch card

Off

Off

- R NO

Off

M1110* Status of SW7 on digital switch card

Off

Off

- R NO

Off

M1111* Status of SW8 on digital switch card

Off

Off

- R NO

Off

M1112* AY0 output point on 2DO card (transistor)

Off

- Off

R/W

NO Off

M1113* AY1 output point on 2DO card (transistor)

Off

- Off

R/W

NO Off

M1115*

Switch for enabling pulse accelerating/decelerating
output (not available in SC_V1.4 and above)

Off

Off

Off

R/W

NO Off

M1116*

Pulse output is accelerating (not available in
SC_V1.4 and above)

Off

Off

Off

R/W

NO Off

M1117*

Accelerating/decelerating pulse output reaches its
target (not available in SC_V1.4 and above)

Off

Off

Off

R/W

NO Off

M1118*

Pulse output is decelerating (not available in
SC_V1.4 and above)

Off

Off

Off

R/W

NO Off

M1119*

Accelerating/decelerating pulse output is completed
(not available in SC_V1.4 and above)

Off

Off

Off

R/W

NO Off

M1120*

Retaining the communication setting of COM2
(RS-485), modifying D1120 will be invalid when
M1120 is set.

Off

Off

- R/W NO Off

M1121

Waiting for the sending of RS-485 communication
data

Off

On

- R NO

Off

M1122 Sending

request

Off

Off

- R/W NO Off

M1123

Receiving is completed

Off

Off

- R/W NO Off

M1124

Waiting for receiving

Off

Off

- R NO

Off

M1125 Communication

reset

Off

Off

- R/W NO Off

M1126

Selecting STX/ETX user defined or system defined

Off

Off

- R/W NO Off

M1127

Sending/receiving data of communication instruction

is completed (RS instruction not included)

Off

Off

- R/W NO Off

M1128 Sending…/receiving...

indication

Off

Off

- R NO

Off

M1129 Receiving

time-out

Off

Off

- R/W NO Off

M1130

Selectin STX/ETX user defined or system defined

Off

Off

- R/W NO Off

M1131

On during MODRD/RDST/MODRW data are
converted to hex data

Off

Off

- R NO

Off

M1132

On when there are no communication related
instructions in the program

Off

- - R NO On

M1133*

Enabling special high-speed pulse output Y0
(50KHz)

SC_V1.4 and above: 2-axis synchronous control,
enabling Y10 output

Off

Off

Off