7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-88

3. How to set up RS-485 communication protocol in D1120

Content

0

1

b0

Data length

7

8

00: None
01: Odd

b1
b2

Parity bits

11: Even

b3

Stop bits

1 bit

2 bits

0001 (H1) :

110

0010 (H2) :

150

0011 (H3) :

300

0100 (H4) :

600

0101 (H5) :

1200

0110 (H6) :

2400

0111 (H7) :

4800

1000 (H8) :

9600

1001 (H9) :

19200

1010 (HA) :

38400

1011 (HB) :

57600 (does not support ES/SS V5.8 and below)

b4
b5
b6
b7

1100 (HC) :

115200 (does not support ES/SS V5.8 and below)

b8

Start word

None

D1124

b9

First end word

None

D1125

b10

Second end word

None

D1126

b15 ~ b11

Not defined

4. When RS instruction is in use, the frequently used communication format in the peripheral device will define the

start word and end word of the control string. Therefore, you can set up the start word and end word in D1124 ~

D1126 or use the start word and end word defined by the PLC. When you use M1126, M1130 and D1124 ~

D1126 to set up the start word and end word, b8 ~ b10 of D1120 have to be set as 1 to make valid the RS-485

communication protocol. See the table below for how to set up.

M1130

0

1

0

D1124: user defined
D1125: user defined
D1126: user defined

D1124: H 0002
D1125: H 0003
D1126: H 0000 (no setting)

M1

12

6

1

D1124: user defined
D1125: user defined
D1126: user defined

D1124: H 003A (’:’)
D1125: H 000D (CR)
D1126: H 000A (LF)

5. Example of how to set up the communication format:

Assume there is a communication format: Baud rate 9600 7, N, 2

STX : “:”

ETX1 : “CR”

ETX2 : “LF”

Check the table and obtain the communication format H788 and write it into D1120.

b15

b0

0 0 0 0 0 1 1 1 1 0 0 0 1 0 0 0

7

8

8

D1120

0

Don t care