2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 141

background image

2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-113

5.

Special D and special M for ID17 ~ ID24 of the 32 stations in EASY EASY PLC LINK (M1353 = On) for

EH/EH2/SV:

MASTER PLC

SLAVE ID 17 SLAVE ID 18 SLAVE ID 19 SLAVE ID 20 SLAVE ID 21 SLAVE ID 22 SLAVE ID 23 SLAVE ID 24

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

M1353 = On: Enable 32 stations in the Link and the function of reading/writing more than 16 data (SET M1353); the
No. of D registers for storing the read/written data.

D1576 D1592 D1577 D1593 D1578 D1594 D1579 D1595 D1580 D1596 D1581 D1597 D1582 D1598 D1583 D1599

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

Number

of data

D1544 D1560 D1545 D1561 D1546 D1562 D1547 D1563 D1548 D1564 D1549 D1565 D1550 D1566 D1551 D1567

start Communication Address

D1512 D1528 D1513 D1529 D1514 D1530 D1515 D1531 D1516 D1532 D1517 D1533 D1518 D1534 D1519 D1535

LINK in SLAVE PLC?

M1440 M1441 M1442 M1443 M1444 M1445 M1446 M1447

Action flag for SLAVE PLC from MASTER PLC

M1456 M1457 M1458 M1459 M1460 M1461 M1462 M1463

“Read/write error” flag

M1472 M1473 M1474 M1475 M1476 M1477 M1478 M1479

“Reading completed” flag (turns “Off” whenever read/write a station is completed)

M1488 M1489 M1490 M1491 M1492 M1493 M1494 M1495

“Writing completed” flag (turns “Off” whenever read/write a station is completed)

M1504 M1505 M1506 M1507 M1508 M1509 M1510 M1511

SLAVE ID 17 SLAVE ID 18 SLAVE ID 29 SLAVE ID 20 SLAVE ID 21 SLAVE ID 22 SLAVE ID 23 SLAVE ID 24

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

Read

out

Write

in

D100

D115

D200

D215

D100

D115

D200

D215

D100

D115

D200

D215

D100

D115

D200

D215

D100

D115

D200

D215

D100

D115

D200

D215

D100

D115

D200

D215

D100

D115

D200

D215

Default start communication address D1512 ~ D1519 to be read = H1064 (D100)

Default start communication address D1528 ~ D1535 to be written = H10C8 (D200)